02 Planning the system
System device selection
Maximum quantity limitation of gateway pass through to an
apartment
Noted: a maximum of 4 gateways can be passed through to
any apartment, regardless of the mode of gateway, except this
combination:building gateway + floor gateway + apartment
gateway. (The looping of gateway is not counted)
For example, for building n Fig.54
» For floor 1 and floor 2, total 3 gateways
» For floor 10, up to 4 gateways, which is the maximum
For each building, a maximum of 2 gateways for each
apartment is allowed, either building gateway + floor gateway,
building gateway + apartment gateway, or floor gateway +
apartment gateway. It is not allowed building gateway + floor
gateway + apartment gateway. So for floor 10, it is not
allowed to have apartment gateway.
Power consumption units of gateway
For gateway except when it is set as line amplifier mode, the
consumption unit is divided into two parts: the one provided
by the internal bus of system controller of one insulated
system , and the other part provided by the external bus of
system controller of the sub insulated system(if any). Fig.55
When set as line amplifier mode, the power consumption is
provided independently by the system controller that controls it.
Please refer to page 61 for Table 1-1 of power
consumption and distance calculation. The power
consumption need to be calculated distinctively by
the mode:
» When it is set as building gateway, floor gateway, apartment
gateway and auxiliary power supply mode, the total
consumption is 7 units, with 2 units (C1) from internal bus
of system controller of the insulated system and 5 units
(C2) from external bus of system controller from system
controller of the other connected insulated system.
» When it is set as line amplifier mode, the consumption unit
is 5 from the system controller that controls it.
Fig.55
Power consumption units of gateway
C2=5 units
C1=2 units
Attenuation unit of gateway
For looping through of one gateway regardless of the mode,
1.5 attenuation unit will be consumed.
Fig.54
Maximum gateways passed through to apartments
Building n
Building 1
46 | ABB-Welcome M
Building 2
ABB-Welcome M | 47