Download System Manual Welcome M
Transcript
02 Planning the system System device selection Maximum quantity limitation of gateway pass through to an apartment Noted: a maximum of 4 gateways can be passed through to any apartment, regardless of the mode of gateway, except this combination:building gateway + floor gateway + apartment gateway. (The looping of gateway is not counted) For example, for building n Fig.54 » For floor 1 and floor 2, total 3 gateways » For floor 10, up to 4 gateways, which is the maximum For each building, a maximum of 2 gateways for each apartment is allowed, either building gateway + floor gateway, building gateway + apartment gateway, or floor gateway + apartment gateway. It is not allowed building gateway + floor gateway + apartment gateway. So for floor 10, it is not allowed to have apartment gateway. Power consumption units of gateway For gateway except when it is set as line amplifier mode, the consumption unit is divided into two parts: the one provided by the internal bus of system controller of one insulated system , and the other part provided by the external bus of system controller of the sub insulated system(if any). Fig.55 When set as line amplifier mode, the power consumption is provided independently by the system controller that controls it. Please refer to page 61 for Table 1-1 of power consumption and distance calculation. The power consumption need to be calculated distinctively by the mode: » When it is set as building gateway, floor gateway, apartment gateway and auxiliary power supply mode, the total consumption is 7 units, with 2 units (C1) from internal bus of system controller of the insulated system and 5 units (C2) from external bus of system controller from system controller of the other connected insulated system. » When it is set as line amplifier mode, the consumption unit is 5 from the system controller that controls it. Fig.55 Power consumption units of gateway C2=5 units C1=2 units Attenuation unit of gateway For looping through of one gateway regardless of the mode, 1.5 attenuation unit will be consumed. Fig.54 Maximum gateways passed through to apartments Building n Building 1 46 | ABB-Welcome M Building 2 ABB-Welcome M | 47