Chapter 4 Parameters

If this parameter is used without DC brake, it will be invalid. Refer to the following
operation timing.
A
zer o
speed
frequency
command
zer o
speed
B=A
output
frequency
RUN/ST OP
RUN
STOP
release
brake
T ime
Multi-function output
(mec hanic al brak e
release)
Pr.02- 11 to 02- 14= 12
mechanical brake
02-32
Control
mode
 Output Current Level Setting for External Terminals
VF
VFPG
Settings

brake
SVC
FOCPG TQCPG
Unit:1
Factory setting: 0
0~100%
When output current is higher or equal to Pr.02-32, it will activate multi-function output
terminal (Pr.02-11 to Pr.02-14 is set to 27).

When output current is lower than Pr.02-32, it will activate multi-function output
terminal (Pr.02-11 to Pr.02-14 is set to 28).
02-33
Control
mode
 Output Boundary for External Terminals
VF
Settings

VFPG
SVC
FOCPG TQCPG
Unit:0.01
Factory setting: 0.00
0.00~+-60.00Hz
When output frequency is higher than Pr.02-33, it will activate the multi-function
terminal (Pr.02-11 to Pr.02-14 is set to 29).

When output frequency is lower than Pr.02-33, it will activate the multi-function terminal
(Pr.02-11 to Pr.02-14 is set to 30).
4-92