Download 0 6 V E - InduProgress
Transcript
Chapter 4 Parameters If this parameter is used without DC brake, it will be invalid. Refer to the following operation timing. A zer o speed frequency command zer o speed B=A output frequency RUN/ST OP RUN STOP release brake T ime Multi-function output (mec hanic al brak e release) Pr.02- 11 to 02- 14= 12 mechanical brake 02-32 Control mode Output Current Level Setting for External Terminals VF VFPG Settings brake SVC FOCPG TQCPG Unit:1 Factory setting: 0 0~100% When output current is higher or equal to Pr.02-32, it will activate multi-function output terminal (Pr.02-11 to Pr.02-14 is set to 27). When output current is lower than Pr.02-32, it will activate multi-function output terminal (Pr.02-11 to Pr.02-14 is set to 28). 02-33 Control mode Output Boundary for External Terminals VF Settings VFPG SVC FOCPG TQCPG Unit:0.01 Factory setting: 0.00 0.00~+-60.00Hz When output frequency is higher than Pr.02-33, it will activate the multi-function terminal (Pr.02-11 to Pr.02-14 is set to 29). When output frequency is lower than Pr.02-33, it will activate the multi-function terminal (Pr.02-11 to Pr.02-14 is set to 30). 4-92