16 of 98 Table 2 – GSC400 Terminal Details Quick Fit Terminals Terminal Wire Size (AWG) 12 12 12 12 12 Current max.* Function Crank 40A Crank Output Terminal Battery + 40A Positive Battery Terminal Battery 40A Negative Battery Terminal Fuel 40A Fuel Output Terminal 1 1 2 40A Extra Relay Configurable Dry Contact 2 Extra Relay Other side of Configurable Dry Contact Speed 1 18 100mA Speed Signal Connection Speed 2 18 100mA Speed Signal Connection *Total controller current output (max 60A) 1 This is a configurable output. See Table 13 on page 59 for possible selections. 2 A normally open SPST relay with user access to both sides of the switch. This is unlike the Fuel and Crank relay outputs which have one side connected internally with battery positive and the opposite side accessible to the user. Analog Inputs Terminal Detail Ground Input 2 Terminal Location 1 2 Wire Size (AWG) 18 18 Current max. 7mA 7mA Function Ground Configurable (Low Resistance, Gain of 1) * Input 3 3 18 7mA Configurable (Low Resistance, Gain of 3) Input 4 4 18 7mA Configurable (Low Resistance, Gain of 3) Input 5 5 18 7mA Configurable (High Resistance, Gain of 3) Input 6 6 18 7mA Configurable (High Resistance, Gain of 1) ** Input 7 7 18 7mA Configurable (High Resistance, Gain of 3) 5V out *** 8 18 7mA Power for electronic sensors. *** * Revision B hardware only. For revision A hardware, this input spec is High Resistance, Gain of 3. ** Revision B hardware only. For revision A hardware this input has a gain of 3. *** Revision B hardware only. For revision A hardware this terminal is a ground. User Manual for the GSC400 Series Automatic Gen-Set Controller