Error detection function Input monitoring and grounding detection When an error is detected between the dual channel inputs, the SG-ONE changes to the Protection state and displays "1" on the error LED display. The conditions to be detected as input errors are shown below. (1) When an input monitoring error detection time (0.1s) is exceeded during the 2 input conditions and they do not match (namely ON/OFF or OFF/ON). (2) When there is an independent condition change of the 1 of the input. (3) The input circuit of the ON state has gone to ground. The input LEDs blink and the monitor output (Ym) supplies pulses (1Hz), to notify the operator of the corresponding input. See Fig. 5-8. Noise detection filter When the SG-ONE is used in an environment with severe noise, the SG-ONE changes to the Stop state and displays "9" on the error LED display. Note: Drive circuit corresponding to the dual channel solid state input (Tn, Tn+1) is always OFF. 5-90