Download Starvert iG5A
Transcript
iG5A Function List Function group 2 LED display H32 H33 H34 H36 H37 H39 Parameter name Rated slip frequency Motor rated current No load motor current Motor efficiency Load inertia rate Carrier frequency select H40 Control mode select H41 H42 H44 H45 2) H46 H47 Auto tuning Stator resistance (Rs) Leakage inductance (Ls) Sensorless P gain Sensorless I gain Sensorless torque limit H48 PWM mode select H49 H50 3) H51 H52 H53 H54 H55 H56 PID control select PID Feedback select P gain for PID controller Integral time for PID controller (I gain) Differential time for PID controller (D gain) F gain for PID controller PID output frequency limit PID output frequency low limit H57 PID standard value select H58 PID control unit select H60 Diagnosis select H61 H62 H63 H64 H65 H66 H67 H70 H71 Sleep delay time Sleep frequency Wake up level KEB drive select KEB action start level KEB action stop level KEB action gain Frequency reference for accel/decel Accel/Decel time scale H72 Power on display H73 Monitoring item select H74 Gain for motor rpm display H75 DB resistor operating rate limit select H76 DB resistor operating rate Description 0~10Hz 1.0~150 [A] 0.1~50 [A] 50~100% 0~2 1~15kHz 0 (Volts/frequency control), 1 (Slip compensation control), 2 (PID feedback control), 3 (Sensorless vector control) 0 (NO), 1 (YES) 0~28 [Ω] 0~300.0mH 0~32767 100~220 [%] 0: Normal PWM mode 1: 2 phase PWM mode 0~1 0 (1: 0~20mA), 1 (V1 0~10V) 0~999.9% 0.1~32.0sec 0.1~30.0sec 0~999.9% 0.1~400Hz Max. frequency 0.1~400 [Hz] 0: Loader digital setting 1 1: Loader digital setting 2 2: V1 terminal setting 2: 0~10V 3: I terminal setting: 0~20mA 4: Setting as a RS-485 communication 0: Frequency [Hz] 1: Percentage [%] 0: Diagnosis disabled 1: IGBT fault/ Ground-fault 2: Output phase short & Output open/ Ground-fault 3: Ground-fault 0~2000 [sec] 0~400 [Hz] 0~100 [%] 0~1 110~140 [%] 110~145 [%] 1~20,000 0 (Based on Max. frequency), 1 (Based on delta frequency) 0 (0.01 sec), 1 (0.1 sec), 2 (1 sec) 0: Frequency command 9: Motor rpm 1: Accel time 10: Inverter DC link voltage 2: Decel time 11: User display select (H73) 3: Drive mode 12: Fault display 4: Frequency mode 13: Direction of motor rotation select 5: Multi-Step frequency 1 14: Output current 2 6: Multi-Step frequency 2 15: Motor rpm 2 7: Multi-Step frequency 3 16: Inverter DC link voltage 2 8: Output current 17: User display select 2 0: Output voltage [V] 1: Output power [kW] 2: Torque [kgf・m] 1~1000% 0: Unlimited 1: Use DB resistor for the H76 set time. 0~30% 1) H32~H36 factory default values are set based on LS motor. 2) Set H40 to 3 (Sensorless vector control) to display this parameter. 3) Set H40 to 2 (PID control) to display this parameter. 28 Factory default – 1) – – – 0 3kHz Adj. during run No No No No No Yes 0 No – – 1000 100 0 180.0 No No Yes Yes No No 0 No 0 No 300% 1sec 0sec 0% 60Hz 0.50 Yes Yes Yes Yes Yes Yes 0 No 0 No 0 No 60.0 0.00 35.0 0 125.0 130.0 1000 0 1 (0.1 sec) No Yes Yes No No No No No Yes 0 Yes 0 Yes 100% Yes 1 Yes 10% Yes