Download MAQ20 PID Controller User Manual

Transcript
MA1056 MAQ20 PID Controller User Manual
Proportional
Set point
+
Process
variable
Error
S
KP
-
S
Controller
output
Integral
KI
ò
Derivative
d
KD
dt
Figure 30: The Parallel Controller Algorithm
The equation of the parallel PID controller algorithm is as follows:
๐‘‘๐ธ
๐ถ๐‘‚ = ๐พ๐‘ƒ × ๐ธ + ๐พ๐ผ โˆซ ๐ธ ๐‘‘๐‘ก + ๐พ๐ท
๐‘‘๐‘ก
Where:
CO is the controller output.
E is the error between process variable and setpoint.
KP is the proportional gain.
KI is the integral gain.
KD is the derivative gain.
Using the noninteractive algorithm is recommended, unless there is a good reason to use the
parallel algorithm.
Control Options
๏‚ท
Gap around setpoint โ€“ with gap control, a lower controller gain can be used when the process
variable is close to setpoint. This will reduce the extent of controller output movements when
the process variable in this area. The Gap around setpoint setting specifies the width of the
gap above and below the setpoint. It is specified in the process variableโ€™s engineering units.
๏‚ท
Gain multiplier inside gap โ€“ the controller gain is multiplied by this factor when the process
variable is inside the gap. A multiplier of 1.0 will have no effect, and a multiplier of 0.0 will
effectively turn off control when the process variable is inside the gap. The latter provides a
deadband.
๏‚ท
PV filter time constant โ€“ a first-order-lag filter (also called a low-pass filter) is provided to reduce
the noise content on the process variable signal. Large-amplitude noise may cause substantial
random movement in controller output which may damage the final control element or affect the
downstream process. A time constant of 0 minutes has no effect. The longer the filter time
constant, the more filtering will be done.
Caution:
Filtering negatively affects the control loopโ€™s dynamic performance and should be used only when
absolutely necessary. If filtering has to be used, the shortest acceptable time constant should be
used. The controller should be retuned after a filter has been added or adjusted.
๏‚ท
Significant digits to display โ€“ This setting specifies the number of significant digits to display on
the faceplate and in the controller settings window.