Download NPT Model User`s Manual for Installation

Transcript
CP-UM-5573E
CAUTION
The MCF air flowmeter uses a µF (Micro Flow) sensor in its sensing unit.
This manual explains the handling precautions, mounting, wiring, setting,
operation and main specifications. See the "Installation &
Configurations" and "Communications" manuals listed below for the
detail handling procedures and the setting methods, etc. These manuals
also contain information on using various functions. Please read if
necessary.
MCF Air Flowmeter USA Model User's Manual for Installation &
Configuration
CP-SP-1293E
MCF Air Flowmeter USA Model User's Manual Communications
CP-SP-1301E
Check the following items when removing the MCF from its package:
Part No.
Q'ty
81424037-001 1
CP-UM-5573E 1
When maintaining or replacing the measurement module, release
the internal pressure of this device before removing the measurement module.
• Horizontal pipe with display facing to the right as seen from
air inlet (Position 2)
MOUNTING
■ Installation location
Flow direction
Avoid mounting this device in places characterized by any of the following:
• Temperature below -10 °C or above 60 °C
• Humidity exceeding 90 % RH
• Sudden changes in temperature, or condensation
• Corrosive or flammable gases
• Heavy concentration of conductive substances (e.g. dust, salt or iron
dust), water droplets, oil mist or organic solvents
• Vibration or shock
• Direct sunlight
• Splashing by water or rain
• Splashing by fluids (e.g. oil, chemicals)
• Constant, heavy splashing by water or dust
• Strong magnetic or electrical fields
■ Piping
Remarks
This Manual
SAFETY PRECAUTIONS
Safety precautions are for ensuring safe and correct use of
this product, and for preventing injury to the operator and
other people or damage to property. You must observe
these safety precautions. Also, be sure to read and
understand the contents of this user's manual.
WARNING
Warnings are indicated when mishandling this
product might result in death or serious injury
to the user.
CAUTION
Cautions are indicated when mishandling this
product might result in minor injury to the user,
or only physical damage to this product.
CFH CF
EV
AL
enter
View from
the air inlet
Side view
Operating
Flow rate range
Instantaneous flow rate deviation
pressure range
0 to 1 MPa
5 to 100 % of full scale flow rate 0.5 % FS per 0.1 MPa ±1 digit or less
-0.07 to 0 MPa 5 to 100 % of full scale flow rate 0.5 % FS per 0.01 MPa ±1 digit or less
Example:
When the MCF is mounted on horizontal piping with the display unit
facing to the right as seen from the air inlet, the instantaneous flow rate
deviation is 1.5 % FS ±1 digit or less as compared with the accuracy in the
normal position at 0.3 MPa.
0.5 % FS / 0.1 MPa × 0.3 MPa = 1.5 % FS
Model
Pipe
Recommended tightening
number
size
torque [N•m]
MCF0080
1/4 inch
12 to 14
MCF0150/0151 1/2 inch
31 to 33
MCF0250
1 inch
36 to 38
MCF0400
1 1/2 inch
59 to 61
MCF0500
2 inch
74 to 76
Side view
Operating
Flow rate range
Instantaneous flow rate deviation
pressure range
0 to 1 MPa 5 to 100 % of full scale flow rate -0.5 % FS per 0.1 MPa ±1 digit or less
-0.07 to 0 MPa 5 to 100 % of full scale flow rate -0.5 % FS per 0.01 MPa ±1 digit or less
Example:
When the MCF is mounted a horizontal piping and the display unit faces
the left from the air inlet, the instantaneous flow rate deviation is -1.5 %FS
±1 digit or less as compared with the accuracy in the normal position at
0.3MPa.
-0.5 % FS / 0.1 MPa × 0.3 MPa = -1.5 % FS
• Horizontal pipe with display facing downward (Position 4),
vertical pipe (Position 5)
The characteristics of the MCF do not change as compared with the
normal position. However, if the MCF is mounted on horizontal piping
with the display unit facing downward, accuracy might decrease due to
accumulated moisture, mist or dust from the air.
Flow direction
Flow direction
Side view
AL
Flow direction
MCF
EV
1
View from
the air inlet
enter
• Do not allow foreign matter to enter the MCF. If rust, water droplets,
oil mist or dust from the pipe enters the device, measurement error,
control error, or damage may occur. Before installation, be sure to
flush upstream and downstream piping thoroughly to remove foreign
matter.
• Coat the pipe threads with an appropriate amount of sealant except for
the top two threads. Too much sealant might cause measurement error
or damage.
• When connecting a piping element such as a pipe with a different
diameter, a regulator, a filter, or a valve on the upstream side, use the
recommended straight pipe section. Failure to do so could cause a
measuring error.
• If a reducer or tube fitting is connected without a straight pipe section, the display might indicate a negative flow rate even though air is
flowing in the positive direction.
“Straight pipe section” refers to a straight pipe with the same diameter as the MCF port. The following types of pipe are suitable: Carbon
Steel Pipes for Ordinary Piping (JIS G3452), ANSI schedule 40 or
less; Carbon Steel Pipes for Pressure Service (JIS G3454), or ANSI
schedule 40 or less; Stainless Steel Pipes (JIS G3459).
Flow direction
CFH CF
Never allow gases that are within explosive limits to pass through
this device. Doing so could result in an explosion.
Do not use this device for oxygen gas. Doing so could result in a
serious accident.
mode
mode
WARNING
MCF
• Horizontal pipe with display facing to the left as seen from
air inlet (Position 3)
• The MCF is a precision instrument. Do not drop it nor subject it to
shock.
• Install so that the direction of gas flow matches the arrow on the side
of the MCF.
• Do not apply force to the measurement module during installation.
• When attaching the MCF to the pipe, fix the MCF in place and rotate
the pipe to the recommended tightening torque.
● Filter
• If there is a possibility of foreign matter entering the device, install a
filter, strainer or mist trap upstream capable of eliminating foreign
matter larger than 1 µm in diameter.
● Accuracy and straight pipe length
• Connection with different size pipe, valve or filter
“Straight pipe section” refers to a straight pipe with the same
diameter as the MCF port. The following types of pipe are suitable:
Carbon Steel Pipes for Ordinary Piping (JIS G3452), ANSI schedule
40 or less; Carbon Steel Pipes for Pressure Service (JIS G3454), or
ANSI schedule 40 or less; Stainless Steel Pipes (JIS G3459).
If a device that is not listed in the table is installed either upstream or
downstream, contact Yamatake for the length of the straight pipe
section. If reverse flow is also expected, it is necessary to have the
same length of straight pipe downstream as upstream.
Pipe or connected device
Flow direction
Side view
● Cautions for pipe installation
UNPACKING
Name
Unit label
User's Manual
• Normal position on horizontal pipe with display facing
upward (Position 1)
AL
2009 Yamatake Corporation ALL RIGHTS RESERVED
Normally the MCF is mounted on a horizontal pipe with the display unit
facing upward. Though the mounting position is unrestricted,
measurement error might be caused by the display direction.
MCF
Be sure that the user receives this manual before the product is used.
Copying or duplicating this user’s manual in part or in whole is forbidden.
The information and specifications in this manual are subject to change
without notice.
Considerable effort has been made to ensure that this manual is free
from inaccuracies and omissions. If you should find an error or omission,
please contact Yamatake Corporation.
In no event is Yamatake Corporation liable to anyone for any indirect,
special or consequential damages as a result of using this product.
To avoid damaging this device, do not use it outside of the
operating pressure range. Also, do not subject it to a pressure
above its pressure resistance.
● Mounting direction
EV
NOTICE
When carrying the flowmeter or connecting it to the pipe, do not
hold it by the measurement module. Doing so could cause
damage, or the device could drop, causing an injury.
enter
Please read the "Terms and Conditions" from the following URL
before ordering or use:
http://www.yamatake.com/products/bi/order.html
If there is a risk of a power surge caused by lightning, use
Yamatake Corporation's SurgeNon to prevent possible fire or
equipment failure.
CFH CF
Thank you for purchasing the MCF.
Before operating this product described in this User's Manual,
please take note of the following points regarding safety.
Be sure to keep this manual nearby for handy reference.
If damage could result from the abnormal functioning of this
device, include appropriate redundancy in the system design.
mode
MCF Air Flowmeter NPT Model
User's Manual
for Installation
Be sure to use this device within the flow rate range stated in the
specifications. To prevent excessive flow, use a suitable means to
control the supply pressure or use a throttle valve or the like to
control the flow rate.
• Although there are no restrictions of mounting direction, if the MCF
is mounted on a horizontal pipe and the display faces to the side, a
measuring error can be caused by the mounting direction.
Also, if the unit is mounted on a horizontal pipe with the display facing downward, foreign matter (rust, water droplets, oil mist, dust) in
the pipes might accumulate in the sensor, causing measuring error or
damage.
• Do not install this device near the outlet of a compressor or bellows
pipe, or in a location where the regulator or the check valve causes
hunting. Doing so could cause measurement error.
MFF25S mist separator for
MCF0080/0150/0151/0250
(Note 3)
MFF25L mist separator for
MCF0400/0500
(Note 3)
Pipe one size larger in dia.
(connected with reducer)
(Note 4, 5)
MCF0080 3/8 inch→1/4 inch
MCF0150/0151 3/4 inch→1/2 inch
MCF0250 1 1/4 inch→1 inch
MCF0400 2 inch→1 1/2 inch
Pipe one size larger in dia.
(connected with reducer)
(Note 4, 5)
MCF0500 2 1/2 inch→2 inch
Pipe one size smaller in dia.
(connected with reducer)
(Note 4, 6)
MCF0080 1/8 inch→1/4 inch
MCF0150/0151 3/8 inch→1/2 inch
MCF0250 3/4 inch→1 inch
MCF0400 1 1/4 inch→1 1/2 inch
Pipe more than one size
smaller in dia. (connected with
reducer)
(Note 4, 6)
MCF0500 1 1/2 inch→2 inch
Single elbow
(Note 7)
Double elbow
(Note 7)
Ball valve (full-bore type full
open)
(Note 8)
Regulator for MCF0080
(Note 9)
Regulator for MCF0150/0151/
0250/0400/0500
(Note 9)
Air filter
Location in
Straight pipe section for this device
relation to For accuracy within speci- For accuracy
the MCF fication range (±3 % FS) within ±5 % FS
Upstream
10D
(Not required)
Upstream
20D
(Not required)
Upstream
5D
(Not required)
Downstream
(Not required)
(Not required)
Upstream
10D
5D
Downstream
5D
5D
Upstream
20D
5D
Downstream
(Not required)
(Not required)
Upstream
25D
10D
Downstream
5D
5D
Upstream
Downstream
Upstream
Downstream
Upstream
Downstream
Upstream
Downstream
Upstream
Downstream
Upstream
10D
(Not required)
10D
(Not required)
(Not required)
(Not required)
200D
10D
30D
5D
25D
(Not required)
(Not required)
10D
(Not required)
(Not required)
(Not required)
(Not required)
(Not required)
(Not required)
(Not required)
(Not required)
Note 1: Do not connect a carbon steel pipe for pressure service (JIS
G3454) or stainless steel pipe (JIS G3459) that is larger than
schedule 40. Doing so might cause a deterioration of
accuracy. (If the pipe schedule number is larger, the inner
pipe diameter is smaller, resulting in less accuracy.)
Note 2: The approximate size of the connection port (D) is 8 mm for
the MCF0080 (1/4 inch), 15 mm for the MCF0150/0151 (1/2
inch), 25 mm for the MCF0250 (1 inch), 40 mm for the
MCF0400
(1 1/2 inch), and 50 mm for the MCF0500 (2 inch).
Note 3: The straight pipe section lengths given in the right-hand
columns above are for connection of a filter the same size
(internal diameter) as the MCF.
Note 4: MCF models and connecting pipe sizes are shown below.
Model No.
MCF0080
MCF0150/0151
Model No.
MCF0250
MCF0400
MCF0500
▲
●
+
1/8 inch
▲
1/4 inch
●
3/8 inch
▲
3/4 inch
▲
1 inch
●
1/2 inch
3/4 inch
●
+
+
1 1/4 inch 1 1/2 inch
+
▲
●
▲
Pipe one size smaller than the MCF
Pipe the same size as the MCF
Pipe one size larger than the MCF
2 inch
2 1/2 inch
+
●
+
Note 5: The figure below shows an example of the MCF0080
connected with reducers. The accuracy is within the
specification range (±3 % FS).
• Do not rotate the cable where it joins the connector (see figure). Doing so
might rotate the connector, twisting and damaging the wires inside.
Flow rate display
MCF
mode CFH CF EV AL
3/8 inch
enter
mode
CFH CF
EV
● Function settings
Func
Name
No.
C0 1 Key lock
setting
Bolts
MCF
Joint of MCF connector cable
MCF0080
3/8 inch 1/4 inch
PART NAMES AND FUNCTIONS
AL
Settings
00: Unlocked
01: Key locked
enter
When connecting the MCF to a pipe 2 sizes larger than the
MCF port (for example, the MCF0080 to a 1/2 inch pipe), to
determine the straight pipe length use the section of the table
marked “Pipe one size larger in dia. (connected with reducer).”
Note 6: The figure below shows an example of the MCF0150
connected with reducers. The accuracy is within the
specification range (±3 % FS).
MCF0150
3/8 inch
1/2 inch
3/8 inch
20D
Do not connect a smaller size pipe to the MCF without a
straight pipe section. Doing so might cause a reverse flow in
the measurement module, even though there is a regular
forward flow in the main flow path. Therefore the display might
indicate a negative value or an extremely low flow rate
compared with the actual rate.
When connecting the MCF to a pipe 2 sizes smaller than the
MFC port (for example, the MFC0150 to a 1/4 inch pipe), to
determine the straight pipe length use the section of the table
marked “Pipe one size smaller in dia. (connected with
reducer).” In addition, on the upstream side add 5D to the
straight pipe length.
1/4 inch
MCF0150
1/2 inch
1/4 inch
• Before wiring the MCF, be sure to turn the power off.
• Connect a load with a resistance of not more than 300 Ω for the
instantaneous flow rate output.
• Keep water away from the cable and from the end of the connector while
wiring.
• Be sure to check that the wiring is correct before turning the power on.
Incorrect wiring could cause damage or malfunction.
• Power source ground, instantaneous flow rate output common, and event
output common lines are all connected inside this device. If these lines
are connected to an external device through a common power supply,
interference could occur causing device failure or faulty operation.
• Take care that the event output does not exceed the output rating of this
device. If a relay is used, the coil should have a built-in surge absorption
diode. Otherwise device failure could occur.
● Connector
Pin Signal MCF0 _ _ _ _ _ _ D01 _ _ _ _ MCF0 _ _ _ _ _ _ D10 _ _ _ _
number
with 4 to 20 mA output
with RS-485 communications
1
V+
24 Vdc
24 Vdc
2
I+/DB
Instantaneous flow
RS-485
rate output (4 to 20 mA) communications (DB)
3
COM
COM
COM
4
EV/DA
Event output
RS-485
communications (DA)
Key
2
3 4 1
Signal
V+
I+/DB
COM
EV/DA
Line color
Brown
White
Blue
Black
Flow rate display:
This 7-segment LED indicates instantaneous flow rate or integrated flow
amount. For the integrated flow, the first 4 digits and last 5 digits are displayed separately. The 7-segment display also indicates settings in setting
mode and alarm codes when an alarm occurs.
LED lamp:
[CFH] Lights up while instantaneous flow rate is indicated.
[CF]
Lights up while integrated flow is indicated.
[EV]
Synchronized with event output
[AL]
Lights up when an alarm occurs
Keys:
[mode] Changes the display or switches to setting mode, etc.
[ ][ ] Increases/decreases the value of a setting, changes the display
mode, etc.
[enter] Used to finalize function settings and parameter settings
Main flow path:
Connects to pipes. Inlet and outlet are marked
Measurement module:
Removable for maintenance. Can be changed with a new one for the
MCF0250, MCF0400 and MCF0500.
Display unit:
Can be rotated in a plane parallel to the flow path.
Rotates 180° clockwise and 90° counterclockwise,
Counter
clockwise
for viewing from any direction.
Clockwise
1
V
2
I
3
4
2 s or more
22.8 to 25.2 Vdc
[mode] key
Allowable load
resistance
(up to 300 )
COM
2 s or more
Instantaneous flow
rate display
Load
EV
Integrated flow
last five digits
Slave station
DA
Parameter setup
mode
key
2 s or more
[mode] key
Integrated flow
first four digits
key
2 s or more
[mode] key
Peak instantaneous
flow rate display
Lowest instantaneous
flow rate display
● Cautions for wiring
Device information
display
To reset the integrated flow total, press and hold [ ] and [ ] at the same
time for 5 seconds or more while the first or last part of the total flow
amount is indicated on the display.
DB
SG
Note :
FG
Shield
FG
MCF(Slave station)
DA
4
Internal circuit
00
00
[mode] key
■ Resetting totalized flow counter
DB
COM
Terminating
resistor
22.8 to
25.2 Vdc
V+
External connection example
• Connect terminating resistors of
150 Ω±5%, 1/2 W min. at each
end of the transmission line.
• The FG grounding must not be
made at the both shielded wire
ends but only at one location.
• Yamatake’s CMC10L001A000
can be used as a converter of the
host station.
2
• If an alarm occurs, the alarm code and normal indication alternate
every two seconds.
• For details of the peak instantaneous flow rate display, lowest
instantaneous flow rate display, device information display and
maintenance mode, refer to the following user's manual: MCF Air
Flowmeter USA Model User's Manual for Installation and
Configuration (CP-SP-1293E.)
• In the Lights Out mode, all LEDs are off except the “CF (CFH)”
LED. If there is an alarm, the alarm indicator lights up.
C 1 1 Reference
00 to 35 °C (every 1 °C)
temperature
00
C 12 Integrated
flow option
00
00: Integrate only normal flow
01: Integrate both normal
flow and reverse flow
(as a minus)
C 14 Integrated
00: 50 ms
flow pulse
01: 250 ms
width
02: 500 ms
C 15 Analog alarm 00: Not used
output *2
01: Upper level
(variable)
02: Lower level
(fixed)
This setting determines what
is indicated on the flow rate
display after the power is
turned on. After exiting normal
indication mode, the device
enters function setup mode.
00
2 s or more
Shield
FG
Master station
DA
1
00: Disabled
01: Enabled
00: Air, nitrogen (fixed)
00: 0.3 MPa standard
01: 0.1 MPa standard
02: 0.5 MPa standard
03: 0.7 MPa standard
[enter] key
[mode] key
WIRING
3
C07 Event
standby
C08 Gas type
C 10 Operating
pressure
00
No display
Terminating resistor
Normal indication
2
C04 Normal
indication
2 s or more
[mode] key
AL
MCF
EV
enter
CFH CF
mode
2 s or more
[mode] key
[mode] key
External connection example
SG
• Supply a power voltage within the specified range.
• Keep the MCF wiring (conduit) away from power wiring or high voltage
wires.
• When connecting the connector, push the two parts together, and then
tighten the nut by hand to 0.4 to 0.6 N•m. Improper tightening can
damage the MCF, or lead to a loss of the IP65 seal, or allow the
connector to come loose due to vibration.
• Do not pull the cable forcibly, and do not lift the MCF by the cable (pullout strength 40 N max., bending force 20 N max.) Do not bend the cable
repetitively or put a constant pulling stress on it.
key
[mode] key
Function setup
mode
[mode] key
• RS-485 communications
DB
AL
2 s or more
30 Vdc or less
MCF0080 (1/4 inch)
EV
Maintenance
mode
[mode]
Power ON
30 Vdc, 50 mA or less
Internal circuit
CFH CF
When the power is turned on, the normal indication is indicated on the
instantaneous flow rate display.
Normal indication means display of the instantaneous flow rate or integrated
flow and no display, depending on the setting of function setup C04.
[mode] key
Instantaneous flow
rate output
4 to 20 mA
Note 8: This valve does not have an internal throttle. If possible, install
a flow regulating valve downstream from the MCF.
Note 9: A regulator should be 200D away from this device. The pipe
from the regulator to this device may be consist of an air tube
and elbow. However, if the elbow is connected to this device,
use the necessary straight pipe section for the elbow.
Strainght pipe section (1/4 inch)
10D or more
00: Not used
01: Instantaneous flow rate
upper limit
02: Instantaneous flow
rate lower limit
03: Within range for instantaneous flow rate
04: Instantaneous flow rate
upper limit (reversed
output) *1
05: Instantaneous flow rate
lower limit (reversed
output) *1
06: Within range for instantaneous flow rate
(reversed output) *1
07: Set value reached by
integrated flow count-up
08: Set value reached by
integrated flow count-up
(reversed output) *1
09: Zero reached by integrated flow count-down
10: Zero reached by integrated flow count-down
(reversed output) *1
11: Integrated pulse output
(minimum unit) *1
12: Integrated pulse output
(minimum unit ✕ 10) *1
13: Integrated pulse output
(minimum unit ✕ 100) *1
14: Alarm
15: Alarm (reversed output) *1
00: Instantaneous flow rate
indication
01: Integrated flow last five digits
02: Integrated flow first four digits
03: No display
■ State transitions
• 4 to 20 mA output
Double elbow (S-bend)
Distnace from
this device to
the regulator
200D or more
C03 Event
output
Main flow path
Outlet
SETTING AND OPERATION
● Wiring example
Elbow
Unit of instantaneous flow
rate and integrated flow
00: L/min, L
01: m3/h, m3
02: m3/min, m3
03: kg/h, kg
04: CFH, CF
05: CFM, CF
enter
10D
Regulator
C02 Flow rate
units
Inlet
mode
Pin number
1
2
3
4
Note 7: The figures below show examples of connection with a single
elbow and double elbow.
10D
Measurement
module
MCF
Note
• Wire color and pin number for MCF connector cable
25D
Single elbow
Display unit
Connector
Connector nut
5D
Factory
Description
setting
00 Even with the keys locked, it
is possible to cancel the key
lock. If any key is pressed
while the keys are locked,
“LOc.” is displayed.
04 Even if the units are changed,
the current integrated flow
amount will remain as is, and
will not be converted to the
new units. After changing the
units, it is necessary to clear
the current integrated flow
count.
If you change the flow rate
engineering unit, affix the
appropriate unit label (included
with the MCF) on top of the
current label.
If the reference temperature
is changed, the peak value and
the lowest value are reset.
00 Reversed output is high when
the event is OFF and low
when the event is ON.
To cancel the event output
for integrated flow count-up
or countdown, reset the
count or change the event
output type.
Since models with RS-485
communications have no
event output terminals,
the EV LED lamp indicates
an event but not event
output.
If the mounting direction is
Position 2 or Position 3, it is
possible to reduce the error
caused by the mounting
direction by adjusting the
pressure correction value (in
maintenance mode) and the
operating pressure. See
Installation and Configuration
CP-SP-1293E for details.
If the reference temperature
is changed, the peak value and
the lowest value are reset.
00
00
For alarms such as sensor
error or memory error, the
level of current set here is
output.
For these alarms, flow rate
display is “0” while an alarm
occurs.
Settings
Factory
Description
setting
00 There is no communication if
the address remains set at
“00.” Set an address that is not
already being used by another
unit.
02
00 to 99
C 31 Transmission 00: No communication
01: 19200 bps
speed *3
02: 9600 bps
03: 4800 bps
C 32 Communication 00: 8-bit data, Even parity,
conditions *3
Stop bit 1 (RTU)
01: 8-bit data, No parities,
Stop bit 2 (RTU)
02: 7-bit data, No parities,
Stop bit 1 (ASCII)
03: 7-bit data, No parities,
Stop bit 2 (ASCII)
C 33 Communications 00: MODBUS (RTU)
type *3
01: MODBUS (ASCII)
00
AO.20 Flow rate
assignment for
20 mA analog
output *1, *6
Setting range
0 to 400 %FS
equiv. *5
AO.04 Flow rate
assignment for
4 mA analog
output *1, *6
E 1.SP Event 1 instantaneous flow
rate *2
0 to 400 %FS
equiv. *5
0
0 to 400 %FS
equiv. *5
0
E 1.hyS Hysteresis for
event 1 *2
E1.dLY ON delay for
event 1 *3
0 to 10 %FS
(at 1% interval)
0 to 60 s
(at 1 s interval)
1
E2.SP Event 2 instan- 0 to 400 %FS
taneous flow
equiv. *5
rate *2
0
E2.hYS Hysteresis for
event 2 *2
E2.dly ON delay for
event 2 *3
0 to 10 %FS
(at 1% interval)
0 to 60 s
(at 1 s interval)
1
0.100 to 2.000
1.000
CF.
Output correction factor
LfcWt Low flow cutoff 1 to 50 %FS
(at 1% interval)
HI .Lt Upper limit for 100 to 200 %FS
indication
EI .LO Last 5 digits of
integrated flow
(event setup)
EI .HI First 4 digits of
integrated flow
(event setup)
COSt Flow rate cost
multiplier *4
00000 to
99990
20.8
20
0
0
1
200
0
0000 to 9999
0
1.0 to 100.0
100.0
Description
• Factory settings are shown below.
MCF0080 → 200
MCF0150 → 500
MCF0151 → 1000
MCF0250 → 3000
MCF0400 → 6000
MCF0500 → 12000
• The decimal point is not shown in
the setting range. Depending on
the model number the decimal
point is added to the display.
• If the setting is less than 10 % of
the FS flow rate, the desired
output may not be possible. Also,
if the setting is zero, when there
is an alarm the output will be fixed
(unchanging).
• If the flow rate units are changed
in function setup C02, set Ao20
again.
The decimal point is not shown
in the setting range. Depending
on the model number the decimal
point is added to the display.
• Setup is enabled when function
setup C03 is set to 0 1 to 06.
• The decimal point is not shown in
the setting range. Depending
on the model number the decimal
point is added to the display.
• If the flow rate units are changed
in function setup C02, set E1.dLy
again.
• Setup is enabled when function
setup C03 is set to 03 or 06.
• The decimal point is not shown in
the setting range. Depending on
the model number the decimal
point is added to the display.
• If the flow rate units are changed
in function setup C02, set E2.dLy
again.
Settable in increments of 0.001. This
setting affects both indication and
output. If it is changed, the peak
value and lowest value for instantaneous flow rate are cleared.
This setting applies to both normal
flow and reverse flow.
The upper limit for indication can be
set at a lower level than the maximum of 200 %FS. If the flow
exceeds this upper limit, the display
will show only the value specified by
this setting.
Settable when function setup C03
is set to 07 to 10.
ON (OFF)
OFF (ON)
E2.hyS
hysteresis
04: [CFH]
E1.hyS
hysteresis
05: [CFM]
*3.
Event ON delay
The event ON delay sets a delay before the event output turns on.
E1.dLy is for the setup of E1.SP and E2.dly is for the setup of E2.SP.
*4.
Flow rate cost calculation
The flow rate cost calculation is related to the setting for flow rate units
in function setup C02.
4
3.2
Flow rate
• If 4 mA flow rate ≥ 20 mA flow rate, the fixed output for alarm
occurrence is output.
• If the difference between the flow rate assignments for 20 mA and for
4 mA is smaller than the full-scale flow rate, the resulting lower
resolution may make it impossible to get the desired output.
* 2: Event output for instantaneous flow rate
Behavior depends on the setting in function setup C03.
(1) When C03 is set to 0 1 or 04 (instantaneous flow rate upper limit)
If the flow rate exceeds the instantaneous flow rate upper limit,
event output turns on. The point at which event output turns off
involves a hysteresis and is calculated as follows:
Event OFF point = instantaneous flow rate upper limit - hysteresis
Specify the hysteresis as a percentage of the full scale flow rate
(%FS).
Per 1 m
High flow rate
ON (OFF)
Phenomenon
The display does not indicate anything.
•
•
•
•
•
•
•
•
•
● Alarm codes and remedies
Alarm
code
AL40
OFF (ON)
E1.hyS
hysteresis
AL5 1
Event OFF point = instantaneous flow rate lower limit + hysteresis
Specify the hysteresis as a percentage of the full scale flow rate
(%FS).
(3) When C03 is set to 03 or 06 (within range for instantaneous flow
rate)
When E1.SP > E2.SP, the setting for E1.SP is used as the upper
limit and the setting for E2.SP is used as the lower limit. When
E1.SP < E2.SP, the E1.SP setting is the lower limit and E2.SP
setting is the upper limit.
When E1.SP = E2.SP, this function does not operate.
Hysteresis should be set below the lower limit and above the upper
limit. Specify hysteresis as a percentage of full scale flow rate
(%FS). Different hysteresis can be set for the lower limit and the
upper limit.
AL52
AL8 1
Item
Flow rate range
exceeded
E2.SP setting
AL82
Sensor error 2
AL83
Sensor error 3
AL84
Sensor error 4
ALG 1
Memory
error
High flow rate
ON (OFF)
ALG2
OFF (ON)
ALG3
ALG4
E2.hyS
hysteresis
3
Contents
Flow exceeds the upper limit
for indication. Or, the flow
exceeds the reverse flow
rate range.
Registered data error 1 The registered flow path
identifiers are incorrect. Flow
rate cannot be calculated
correctly.
Registered data error 2 The registered properties of
the flow sensor are incorrect.
The flow rate can not be
calculated correctly.
Sensor error 1
The flow signal is outside the
normal range.
• E1.SP setting < E2.SP setting
E1.hyS
hysteresis
•
•
•
Remedy
Check that the supplied power and polarity are correct.
Check that the connector is connected correctly.
Check for air leaks
Check that wiring is correct.
When the MCF is mounted on a horizontal pipe and the display unit
faces the side, zero point drift may be caused by the mounting direction. Set the low flow cutoff to 5 %FS.
If the MCF is mounted where the ambient temperature or the temperature of the measured gas fluctuates widely, the MCF
might detect convection inside the pipe as a flow. Try measuring after the temperature stabilizes.
Check for air leaks.
Check if foreign matter is stuck on the main path orifices. If so, remove it.
After detaching the measurement module from the main path, check if foreign matter is stuck on the main path orifices. If
so, blow it off with compressed air.
After detaching the measurement module from the main path, check if the internal filter is stained. If so, clean it.
Check if foreign substances such as dust or oil are present on the pipe or the connection port of the MCF. If so, ask
Yamatake for repair.
Check that the wiring is correct.
Check if the flow fluctuates widely, or if it greatly exceeds the measurable limit.
High flow rate
ON (OFF)
Parenthesis indicate
the state for reversed output
Can be selected for 4 to 20 mA output models only.
Cannot be selected for RS-485 communications models.
● Remedy for abnormal phenomena
(2) When C03 is set to 02 or 05 (instantaneous flow rate lower limit)
If the flow rate falls below the instantaneous flow rate lower limit,
event output turns on. The point at which event output turns off
involves a hysteresis and is calculated as follows:
E1.SP setting
Notes
The upper limit
of the range
corresponds to
a flow rate of
400 %FS.
The upper limit
0 to 847 0 to 2119 0 to 4238 0 to 12710 0 to 25420 0 to 50850 of the range
corresponds to
0 to 14.10 0 to 35.30 0 to 70.60 0 to 211.90 0 to 423.70 0 to 847.40 a flow rate of
200 %FS.
TROUBLESHOOTING
Note: If the Event OFF point is less than zero, the output turns off
at zero.
Parenthesis indicate
the state for reversed output
MCF0250 MCF0400 MCF0500
0 to 12000 0 to 24000 0 to 48000
0 to 720.0 0 to 1440.0 0 to 2880.0
0 to 12.000 0 to 24.000 0 to 48.000
0 to 931.0 0 to 1862.0 0 to 3724.0
Per 1000 CF
Measurement error has increased and
exceeds the accuracy specifications.
E1.SP setting
Low flow rate
MCF0150 MCF0151
0 to 2000 0 to 4000
0 to 120.0 0 to 240.0
0 to 2.000 0 to 4.000
0 to 155.2 0 to 310.4
Per 1 kg
•
E1.hyS
hysteresis
*6.
3
OFF (ON)
Parenthesis indicate
the state for reversed output
MCF0080
0 to 800
0 to 48.0
0 to 0.800
0 to 62.1
If the setting exceeds the upper limit for indication, the instantaneous
flow rate output will be equivalent to the upper limit for indication.
Do not set values for Event 1 instantaneous flow rate or Event 2
instantaneous flow rate that exceed the upper limit for indication. The
instantaneous flow rate may not reach the set value, so that the event
does not operate.
Unit of flow rate cost calculation
Shutting the front and back valves of the
MCF, etc., the actual flow rate should be
zero, but the flow rate display does not
indicate zero.
E1.SP setting
Low flow rate
C02 setting
00: L/min, L
01: m3/h, m3
02: m3/min, m3
03: kg/h, kg
04: CFH, CF
05: CFM, CF
Setting range
The setting range depends on the model number and the flow rate
indication units. See the table below.
C02 setting
00: [L/min]
01: [m3/h]
02: [m3/min]
03: [kg/h]
High flow rate
Output range
of 4-20 mA
Low flow rate
This setting is used to indicate cost
in the device information display.
*5.
E1.SP setting
Low flow rate
Parenthesis indicate
the state for reversed output
[Flow rate assignment for 4 mA] [Flow rate assignment for 20 mA]
Factory
setting
Depends
on model
number
E2.SP setting
Where:
4 mA flow rate: Flow rate assignment for 4 mA analog output
20 mA flow rate: Flow rate assignment for 20 mA analog output
• The minimum output for reverse flow is 3.2 mA and the maximum
output for normal flow is 20.8 mA.
00
● Parameter settings
Name
(Indicated flow rate – 4 mA flow rate)
× 16 + 4 mA
(20 mA flow rate – 4 mA flow rate)
Output current =
For RTU, select “00” or “01”
due to 8-bit data processing.
For ASCII, select “02” or “03”
due to 7-bit data processing.
(If RTU is selected, 8-bit data
processing is always applied
even though “02” or “03” is
chosen).
* 1: If selected for RS-485 communications models, no communications
begin.
* 2: Cannot be selected for RS-485 communications models.
* 3: Can be selected for RS-485 communications models only.
Item
• E1.SP setting > E2.SP setting
Note: If Event OFF point is less than zero, the output turns off at
zero.
* 1: Analog output scaling
The output current is calculated as follows:
Current output [mA]
Func
Name
No.
C 30 Device
address *3
Device
data error
Property
error
Setup data
error
Integrated
data error
Causes
A forward or reverse flow exceeds
the specified range.
Wrong flow path identifiers setting.
The registered properties might be
corrupted.
The flow signal can decrease greatly if
foreign matter causes a short circuit or
if there is an excessive reverse flow.
The flow signal may differ
The sensor might be broken or the
from the actual flow.
output level might have decreased.
Foreign matter or condensation may
be present on the sensor.
Sensor heater voltage is
The sensor may be broken or foreign
outside the normal range.
matter may be stuck to it, causing a
short circuit.
Checksum error during
Data might be corrupted by electrical
EEPROM read/write process. noise.
Remedy
Check for excessive flow. If a minus sign is shown on the flow rate display
when the alarm occurs, there might be a reverse flow. Correct the factor
causing the reverse flow.
When the actual flow enters the normal range, the alarm lamp should turn off.
Set the correct flow path identifiers in maintenance mode. If the MCF does
not return to normal after the setting is changed, reboot it. If the MCF does
not return to normal after being restarted, call for repair.
If the MCF does not return to normal after rebooting, call for repair.
If the cause of this alarm is excessive reverse flow, the MCF will return to
normal automatically when the flow falls within the measurable range.
If the alarm does not turn off in spite of a normal reverse flow, ask for repair.
If the MCF does not return to normal after a few hours of dry air flow, call for
repair.
If the MCF does not return to normal after a few hours, call for repair.
If the MCF does not return to normal after rebooting, call for repair.
EEPROM write process might have
Try data setup again. If the MCF does not return to normal after rebooting,
ended abnormally due to power outage. call for repair.
After resetting the integrated flow, if the MCF does not return to normal after
rebooting, call for repair.
MODEL SELECTION GUIDE • OPTIONAL PARTS
■ Optional parts (sold separately)
Option
0
D
Y
D01
D10
080
150
151
250
400
500
None
Inspection certificated provided
Complying with the traceability
certification
Power supply, communications, output
24 Vdc, no communications, 4 to 20 mA output
24 Vdc, RS-485 communications, no output
Pipe size
8 A (1/4 inch)
15 A (1/2 inch)
15 A (1/2 inch)
25 A
(1 inch)
40 A(11/2 inch)
50 A
(2 inch)
•
•
•
•
•
•
•
Flow rate range
200 L/min
500 L/min
1000 L/min
3000 L/min
6000 L/min
12000 L/min
Model number
Cable
length
Cable with
PA5-4ISX2MK-E
2m
connector
PA5-4ISX3MK-E
3m
exclusive for
PA5-4ISX5MK-E
5m
MCF series
PA5-4ISX2HK-E
2m
PA5-4ISX3HK-E
3m
PA5-4ISX5HK-E
5m
Extension
PA5-4ISB2MK-E
2m
cable with
PA5-4ISB3MK-E
3m
connector
PA5-4ISB5MK-E
5m
PA5-4ISB2HK-E
2m
PA5-4ISB3HK-E
3m
PA5-4ISB5HK-E
5m
Name
Mounting bracket
Measurement module
Cable properties
Oil resistant, bend-tolerant
Flame-resistant cable
UL2464
EN-compliant
Oil resistant,
Flame-resistant cable
UL2464
EN-compliant
Oil resistant, bend-tolerant
Flame-resistant cable
UL2464
EN-compliant
Oil resistant,
Flame-resistant cable
UL2464
EN-compliant
Model number
81446721-001
81447192-203
81447192-223
Lead
color
1 - Brown
2 - White
3 - Blue
4 - Black
Response time
RS-485 communications
(RS-485 communications models only)
Event output
(Not available for RS-485 communications models)
Data storage
Dielectric strength
Description
For MCF0080/0150/0151/0250
For MCF0250/0400/0500
(4 to 20 mA output models)
For MCF0250/0400/0500
(RS-485 communications models)
Insulation resistance
Protective structure
Standards compliance
Mass
EXTERNAL DIMENSIONS
SPECIFICATIONS
Notes: 1.
2.
3.
4.
5.
6.
MCF0400/0500
Unit : mm
(90)
(78)
MCF cable connector
MCF
MCF cable connector
mode
CFH CF
MCF
mode
CFH CF
EV
EV
AL
enter
AL
enter
Connector
(M12)
(4.5)
Mounting bracket
(H2)
H1
Connector
(M12)
H4
H3
(H2)
(8)
L
47
2-M4, Thread depth 7
(Retaining screws)
L
W2
W1
61
23.5
48
24
Connection
type and size D
2-M5, Thread depth 7
(Retaining screws)
30.5
Connection
type and size D
-0.5 %FS / 0.1 MPa ±1 digit or less (5 to 100 % of FS flow rate)
34
13.5
17
0.5 %FS / 0.01 MPa ±1 digit or less (5 to 100 % of FS flow rate)
27
Full scale (FS) flow rate [L/min]
Minimum sensitivity [L/min]
Indication resolution
Instantaneous flow rate
[L/min] (Note 1)
Integrated flow
Maximum display range [L/min]
[m3/h]
[m3/min]
[kg/h]
[CFH]
[CFM]
Indication accuracy for instantaneous flow rate
Indication repeatability for instantaneous flow rate
Temperature characteristics
Pressure characteristics Operating pressure
for instantaneous flow
0 to 1 MPa
rate
Operating pressure
-0.07 to 0 MPa
Pressure characteristics Operating pressure
of instantaneous flow
0 to 1 MPa
rate for Position 2
Operating pressure
mounting (Note 2)
-0.07 to 0 MPa
Pressure characteristics Operating pressure
of instantaneous flow
0 to 1 MPa
rate for Position 3
Operating pressure
mounting (Note 3)
-0.07 to 0 MPa
Operating pressure range
Operating temperature range
Operating humidity range
Storage temperature range
Storage humidity range
Pressure resistance
Allowable leakage rate
Connecting bore, standard
Material of gas flow
Main flow path
passage
Measurement module
Packing
Material of measurement module case
Rated voltage
Power supply range
Current consumption
MCF0080/0150/0151/0250
(75)
(63)
Measured gas
MCF0080
MCF0150
MCF0151
MCF0250
MCF0400
MCF0500
Air, Nitrogen Gas must be dry and not contain corrosive components such as chlorine, sulfur and acid. Gas must be a
clean, without dust or oil mist.
200
500
1000
3000
6000
12000
2
5
10
30
60
120
1
1
2
5
10
10
10
10
10
10
100
100
-60 to +400
-150 to +1000
-300 to +2000
-900 to +6000
-1800 to +12000
-3600 to +24000
-3.6 to +24.0
-9.0 to +60.0
-18.0 to +120.0
-54.0 to +360
-108.0 to +720.0
-220.0 to +1440.0
-0.060 to +0.400
-0.150 to +1.000
-0.300 to +2.000
-0.900 to +6.000
-1.800 to +12.000
-3.600 to +24.000
-4.7 to +31.0
-11.6 to +77.6
-23.2 to +155.2
-70 to +465.5
-140.0 to +931.0
-279.0 to +1862.0
-127 to +848
-318 to +2119
-736 to +4238
-1905 to +12715
-3810 to +25430
-7630 to +50850
-2.12 to +14.12
-5.30 to +35.30
-10.6 to +70.6
-31.5 to +211.5
-63.5 to +423.50
-127.0 to +847.1
±3 %FS ±1 digit (except 2 % or less of FS flow rate) (Note 4, 5, 6)
±1 %FS ±1 digit (2 to 100 % of FS flow rate)
±0.15 %FS / °C ±1 digit or less
-0.25 %FS / 0.1 MPa ±1 digit or less (2 to 40 % of FS flow rate)
-0.55 %FS / 0.1 MPa ±1 digit or less (40 to 100 % of FS flow rate)
±0.25 %FS / 0.01 MPa ±1 digit or less (2 to 40 % of FS flow rate)
±0.55 %FS / 0.01 MPa ±1 digit or less (40 to 100 % of FS flow rate)
0.5 %FS / 0.1 MPa ±1 digit or less (5 to 100 % of FS flow rate)
H1
Item
H3
Name
MCF 0 _ _ _ ANN _ _ _ 00 _ 0
MCF0080
MCF0150
MCF0151
MCF0250
MCF0400
MCF0500
50 ±5 ms (factory setting)
Current output: 4 to 20 mA (3.2 to 20.8 mA of output range)
Output at alarm occurrence (upper): 21.6 ±0.4 mA (factory setting, variable by function setup)
Output at alarm occurrence (lower): 0.0 ±0.4 mA (fixed)
Accuracy: Indication for instantaneous flow rate ±0.5 % FS ±1 digit
Allowable load resistance: 300 Ω max.
Maximum output current: 24 mA max.
1.5 s max. (time until 95 % of final value for response to 0 to 100 %FS step input, with 50 ms measurement cycle)
Transmission line :
3-wire system
Transmission speed : 4800, 9600, 19200 bps
Protocol :
MODBUS
NPN open collector: 30 Vdc, 50 mA max
Selectable from following functions:
• Instantaneous flow rate switch (upper limit, lower limit, within range)
• Integrated flow switch (count-up, countdown)
• Integrated pulse output (3 assignable pulse weights)
• Alarm output
EEPROM non-volatile semiconductor memory
1 mA or less of leak current when 500 Vac is applied for 1 s between contacts of connector and main flow path or
mounting bolts.
50 MΩ or more between contacts of connector and main flow path or mounting bolts, with 500 Vdc megger
IP65 (JIS C0920 and IEC529) ingress protection for indoor installation
EN61326-2-3: 2006, EN61326-1:2006
Approx. 400 g
Approx. 400 g
Approx. 400 g
Approx. 500 g
Approx. 700 g
Approx. 1.1 kg
H4
■ Model selection guide
Item
Measurement cycle
Instantaneous flow rate output
(Not available for RS-485 communications models)
-0.5%FS/0.01MPa ±1digit or less (5 to 100% of FS flow rate)
-0.07 to +1.0 MPa (gauge pressure)
-10 to +60 °C (without freezing)
0 to 90 % RH (without condensation)
-20 to +70 °C (without freezing)
0 to 90 % RH (without condensation)
1.5 MPa (gauge pressure)
100 mL/h (at internal pressure of 1.5 MPa)
1/4 "NPT
1/2 "NPT
1/2 "NPT
Aluminum alloy (alumite treatment)
SUS304, PBT, H-NBR (hydrogenated nitrile rubber)
H-NBR (hydrogenated nitrile rubber)
Modified PPO
24 Vdc
22.8 to 25.2 Vdc
120 mA max.
H1
H2
H3
H4
L
D
1 "NPT
1 1/2 "NPT
MCF0080
65.8
46.5
34
15
75
1/4 "NPT
MCF0150/0151
65.8
46.5
34
15
75
1/2 "NPT
MCF0250
79.8
60.5
48
23.5
90
1 "NPT
H1
H2
H3
H4
L
W1
W2
D
2 "NPT
MCF0400
93.8
74.5
62
30
100
60
30
1 1/2 "NPT
MCF0500
106.8
87.5
75
37.5
110
75
37.5
2 "NPT
Specifications are subject to change without notice. (08)
The indication resolution shows the smallest displayable digit, regardless of the position of the decimal point or the flow rate units.
Horizontal piping with the display facing right as seen from the air inlet (Position 2)
Horizontal piping with the display facing left as seen from the air inlet (Position 3)
Measuring accuracy becomes ±5 %FS ±1 digit after the measurement module is reassembled.
The measuring accuracy becomes ±5 %FS ±1 digit after the measurement module is replaced with a new one. (For MCF0250, MCF0400 and MCF0500)
Do not connect a carbon steel pipe for pressure service (JIS G3454) or stainless steel pipe (JIS G3459) that is larger than schedule 40. Doing so might cause
a deterioration of accuracy. (If the pipe schedule number is larger, the inner pipe diameter is smaller, resulting in reduced accuracy.)
Advanced Automation Company
1-12-2 Kawana, Fujisawa
Kanagawa 251-8522 Japan
URL: http://www.azbil.com
4
1st Edition: Issued in Feb. 2009 (M)
2nd Edition: Issued in June 2009 (M)