Transcript
6.3 Local Parameter Setting WARNING The local push button on the integral indicator must not be used in a hazardous area. When it is necessary to use the push button, operate it in a non- hazardous location. 39 <6. Operation> 6.3.1 Local Parameter Setting (LPS) Overview Parameter configuration by the external adjustment screw and push button (integral indicator code E) offers easy and quick setup for parameters of Tag number, Unit, LRV, URV, Damping,Output mode (linear/square root), Display out 1, and Re-range by applying actual pressure (LRV/URV). There is no effect on measurement signal (analog output or communication signal) when Local Parameter Setting is carried out. IMPORTANT • Do not turn off the power to the transmitter immediately after performing parameter setting. Powering off within 30 seconds of performing this procedure will return the parameter to its previous setting. • The parameter of Ext SW must be“Enabled” to perform this configuration. See the user’s manual IM 01C25T (HART/BRAIN) for the setting procedure. • The Local Parameter Setting function is available with HART or BRAIN communication type. External adjustment screw cover F0604.ai Figure 6.3 External Adjustment Screw Integral indicator 6 Push-button Figure 6.4 Range –Setting Switch (push button) IM 01C25A01-01E Operation F0605.ai