INSTALLATION INSTRUCTIONS
3.9.3.2 Flue type KIT FK 100 – cod. 82280LP
Vertical flue kit Ø100 mm in polypropylene .
Discharges exhaust fumes and draws air directly from high Level.
800
Ø100
Fig. 1
MAXIMUM FLUE LENGTH
The maximum flue length (linear equivalent) is obtained:
a. Through the sum of individual components flue lengths (linear equivalent) that must be lower than 15 m;
N.B. A 30 mt maximum flue length can be reached by setting the parameters’ value to 180 Hz. Operate
according to the instructions of “5.3 Setting the parameters” to modify the parameters’ value.
b. Through the sum of individual components’ flue efficiency losses, that must be lower than 146 Pa.
The maximum flue length can be obtained according to the following table:
Equivalent lenght
m
Flue efficiency loss
Pa
1
5.8
0.5
2.9
90° Flue bend Ø100 MF polypropylene
3
17.5
45° Flue bend Ø100 MF polypropylene
1.4
7.8
Description
Extension Ø100 L = 1000 mm MF polypropylene
Vertical connector Ø100 w/test point MF polypropylene
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4