Download E3 and E3 Plus Solid-State Overload Relay User Manual
Transcript
DeviceNet™ Node Commissioning TIP Chapter 4 If the screen appears as shown below, continue with Building and Registering an EDS file. 5. If RSNetWorx software recognizes the device as an E3 Overload Relay, skip ahead to the following section – Using the Node Commissioning Tool of RSNetWorx for DeviceNet. TIP Node Commissioning can also be accomplished by using the DeviceNet Configuration Terminal, Cat. No. 193-DNCT. Building and Registering an EDS File The EDS file defines how RSNetWorx for DeviceNet will communicate to the E3 Overload Relay. The EDS file can be created over the DeviceNet network or downloaded from the Internet. NOTE: If you are using DeviceLogix functionality, you must download the EDS file from www.ab.com/networks/eds. Perform the following steps to build and register the EDS file. 1. Right-click the Unrecognized Device icon. The Register Device menu appears. 2. Select Yes. The EDS Wizard will appear. 3. Select Next, then Create an ESD File. 4. Select Next. 5. Select Upload EDS. 6. Select Next. The EDS Wizard screen appears:. Rockwell Automation Publication 193-UM002I-EN-P - December 2011 97