Download Ring Main Units
Transcript
CTD (Condenser trip device) (For discharge) AC input DC output CTD is built as standard in the contactor with AC control of instantaneous excitation so that the contactor can be tripped within 30 seconds in the event of an electricity failure. The automatic trip circuit in the event of an electricity failure is to be built by a customer. Rating Description Type CTD-100 CTD-200 Rated input voltage(V) AC 100/110 AC 200/220 50/60 50/60 140/155 280/310 Within 5 sec. Within 5 sec. Max. 30 sec. Max. 30 sec. Input voltage range 85%~110% 85%~110% Capacitor rating(μ F) 400 160 Frequency(Hz) Rated impulse voltage(V) Charging time Trip command possible time Control circuit diagram Terminal Closing coil (C) Shunt coil (TC) The coil operated only when the power is applied continuously over 45ms. It has built-in electrically antipumping circuit. When the VCB is 'ON' position, even though the control power of a shunt coil is 'OFF', the VCB maintains the 'ON' position. Rated voltage Rated current (A) Rated voltage Rated current (A) DC 24V 10 DC 24V 10 DC 110V 2.5 DC 110V 2.5 Note 1) Range of the normal operating voltage: 85~110% 2) DC 24V is the underdeveloped rating. Control connector Voltage detector Screw type 09 11 08 19 10 07 18 06 17 03 05 02 14 04 01 13 Plug in type 12 GAS pressure gauge Note 1) Range of the normal operating voltage: 70~110% 2) DC 24V is the underdeveloped rating. 23