Download User Manual - LUCKINSlive
Transcript
Operating Modes Operating Modes for Pulse and Incremental Encoders Overview Operating modes 1 ... A are described below. Operating Mode 1: Down Counter for Pulses In this operating mode, all pulses of counter input A are used for down counting, beginning from a preset value (default = 0). Counter input B has no function. Pulse encoders with 5V differential output as well as pulse encoders with 24V single ended output (24V initiators) can be connected. Two digital outputs can be controlled using two programmable threshold values. See the example Up Counter (Mode 2) (see page 104). Operating Mode 2: Up Counter for Pulses In this operating mode, all pulses of counter input A are used for up counting, beginning from a preset value (default = 0). Counter input B has no function. Pulse encoders with 5V differential output as well as pulse encoders with 24V single ended output (24V initiators) can be connected. Two digital outputs can be controlled using two programmable threshold values. See the example Up Counter (Mode 2) (see page 104). Operating Mode 3: Reserved Corresponds with operating mode 0. Operating Mode 4: Counting with Incremental Encoder with 1/1 Logic Position measurement with incremental encoders is carried out according to the counting procedure. The measuring system must therefore be reset after switching on or power failure. The encoder transmits a reference signal (zero pulse) to do this. In order to identify the direction of spin when counting up or down, the incremental encoder sends two periodical square wave signals in quadrature, which are evaluated by the 170 AEC 920. Two digital outputs can be controlled using two programmable threshold values. 33001466 06/2011 25