Download CX-Supervisor User Manual
Transcript
OMRON CHAPTER 16 – Using CX-Supervisor as an OPC Client name is overwritten. The default name for new groups are Group1, Group2 etc. Update Rate: – This is the rate at which the Items (data points) in the group will be interrogated and new data entered if it is a readout, or read from if it’s a control. Enter the rate as a numerical value and select the units from the drop down list. The minimum value is 100msec; the maximum is 99999Sec i.e. over 27 hours. Active On Startup: – Checking this option will make the Group active when the OPC server is started. This means the items contained within will be able to read and write data. The default is checked. c) Items Tab The Items within the selected group are listed. Items are data points of information stored in the OPC Server. The Item Attributes dialog can be used to add or edit the items. Note: This dialog cannot be opened until at least one group is added. i) ITEM ATTRIBUTES The Item Attributes dialog enables you to define the attributes of each Item (data point) in the selected group. Name: – This is the client name for an Item i.e. a point of data. Item ID: – This is the OPC Server’s name for the data. If the server supports OPC item browsing facilities, click Browse to browse the OPC Server to list the namespace groups and items to create the OPC Item ID. Otherwise, type the OPC Item ID in the format specified in the server documentation. Access Path: – This is the full path name for the data point. Consult the documentation for the server to determine the correct format. Release 3.0 Page (267)