If the following errors occur on the A/D converter module while data is written to or read from the CPU module, the
corresponding error code below is stored in Latest error code (Un\G19).
The error is reported to the CPU module also.
Error code
Description and cause of error
(decimal)
The input range is set with a value outside the setting range for
10
Switch 1 of the intelligent function module switch setting.
The channel with the invalid setting fits in .
11
Action
Set a valid value on the intelligent function module
switch setting in the parameter setting.
Power off and on the module.
111
A hardware failure has occurred on the module.
If the error occurs again, a failure might have
occurred on the module. Please consult a local
Mitsubishi representative.
112
A value other than 0 is set to Switch 5 on the intelligent function
Set 0 to Switch 5 on the intelligent function module
module switch setting.
switch setting in the parameter setting.
Check the digital output value.
113*1
The data in the flash memory has a problem.
If there is a problem of the digital output value,
please consult a local Mitsubishi representative.
Start over the offset/gain setting of all channels
120*1
An invalid value is set to the offset/gain setting.
The channel where the error has occurred cannot be identified.
where the user range setting is used.
If the error occurs again, a failure might have
occurred on the module. Please consult a local
Mitsubishi representative.
Start over the offset/gain setting of the channel
An invalid value is set to the offset/gain setting.
The channel where the error has occurred fits in .
where the error has occurred.
If the error occurs again, a failure might have
occurred on the module. Please consult a local
Mitsubishi representative.
161*1*2
The G(P).OGSTOR instruction was executed in the offset/gain
Do not execute the G(P).OGSTOR instruction in the
setting mode.
offset/gain setting mode.
• The G(P).OGSTOR instruction has been consecutively
162*1
executed.
• For the offset/gain setting, a setting value has been
consecutively written to the flash memory more than 25 times.
• The G(P).OGSTOR instruction has been executed on a
module different from the one on which the G(P).OGLOAD
163*1
instruction was executed.
• The G(P).OGSTOR instruction has been executed ahead of
the G(P).OGLOAD instruction.
170*1
per module.
• Write the setting value into the flash memory only
once for each offset/gain setting.
• Execute the G(P).OGLOAD and G(P).OGSTOR
instructions to the same module.
• After executing the G(P).OGLOAD instruction on
the module from where data is restored, execute
the G(P).OGSTOR instruction on the module to
where the data is restored.
The offset/gain setting was configured exceeding the maximum
No more offset/gain setting is reflected on the
number of times.
operation successfully.
When Channel change request (YB) turns on in the offset/gain
171*1
• Execute the G(P).OGSTOR instruction only once
setting mode, a value other than User range setting (uni-polar:
current) or User range setting (bi-polar: voltage) is set in the input
range setting.
Set User range setting (uni-polar: current) or User
range setting (bi-polar: voltage) in the input range
setting.
The averaging time value set in CH Time Average/Count
Average/Moving Average/Time lag filter constant (Un\G1 to
20*1
Un\G4) is outside the range of 2 to 5000ms.
The channel where the error has occurred fits in .
Set the averaging time to a value within the range of
2 to 5000ms.
221
11.4 Error Code List
12
*1