SELCO A/S
UNLOADTRIP
SIGMA S6000 IO/P Module
The output activates as soon as an UNLOAD command is active and the
generator load passes below UNLOAD TRIP LEVEL.
7.7 Open collector protection outputs
The open collector protection outputs are placed on the C/B TRIP CAUSE & GND connector of the
S6000 Module. These outputs can be used for external indication of alarms. On earlier firmware
versions (before 071112) these outputs were fixed (terminal 1 = SC, terminal 2 = OC, terminal 3 =
OL, terminal 4 = RP, terminal 5 = EL, terminal 6 = VE). From FW 071112 the functions of these
outputs can be configured. It is possible to assign more than one function to one output, thus it is
possible to configure common alarms.
Each function has one command line. The function can be set by the command line followed by a
choice. The choice can be OFF for deactivation of this function or the output number: OFF, OC1,
OC2, OC3, OC4, OC5, OC6.
WRITE OCPROTOUT SC [OFF, OC1, OC2, OC3, OC4, OC5, OC6](OC1)
WRITE OCPROTOUT OC [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC2)
WRITE OCPROTOUT OL [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC3)
WRITE OCPROTOUT RP [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC4)
WRITE OCPROTOUT EL [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC5)
WRITE OCPROTOUT VEUPPER [OFF, OC1, OC2, OC3, OC4, OC5, OC6(OC6)]
WRITE OCPROTOUT VELOWER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC6)
WRITE OCPROTOUT FEUPPER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC6)
WRITE OCPROTOUT FELOWER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OC6)
WRITE OCPROTOUT BUSVEUPPER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OFF)
WRITE OCPROTOUT BUSVELOWER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OFF)
WRITE OCPROTOUT BUSFEUPPER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OFF)
WRITE OCPROTOUT BUSFELOWER [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OFF)
WRITE OCPROTOUT BUSFD [OFF, OC1, OC2, OC3, OC4, OC5, OC6] (OFF)
7.8 Analogue Outputs
The analogue outputs are configured with the following parameters.
Revision: 06.03.2008