Download "user manual"
Transcript
5 PROGRAMMING (3) Program example Checking connection status of the AJ65SBT2B-64DA Reads data link status. Turns on MC contact (M100) when data link is normal. Turns on Y60 when a data link error occurs. Initial setting CH1 Output range setting (RY04 to RY06): 0 (-10 to 10V) CH2 Output range setting (RY07 to RY09): 1 (0 to 5V) CH1 HOLD/CLEAR setting (RY10): HOLD CH2 HOLD/CLEAR setting (RY11): HOLD CH1 Conversion enable/disable setting (RY14): Enable CH2 Conversion enable/disable setting (RY15): Enable Turns on Initial data processing completion flag (RY18). Turns on Initial data setting request flag (RY19). Changing initial setting CH1 Conversion enable/disable setting (RY14): Disable CH2 Conversion enable/disable setting (RY15): Disable Turns on Initial data setting request flag (RY19). Processing for completing initial setting Turns off Initial data processing completion flag (RY18). Turns off Initial data setting request flag (RY19). Figure 5.7 Program example (when the QCPU (Q mode) is used) 1/2 * 1: The program in the dotted area is required only when the initial setting is changed. 5-6 5.3 Program Example When the QCPU (Q mode) is Used