Download RX User Manual
Transcript
RX Series Digital Solid State Protection Relay 5 - 2000A 5.6.6 Lockout Features F044 – F046 provide lockout protection for motors and equipment that may have potentially damaging consequences from premature restart or with limited duty cycles. Time and count values for these lockouts can be viewed in F081 – F085. Time values are based on the Real Time Clock and DO NOT reset when power is lost or disconnected. Emergency clearing of lockouts can be accomplished in F071. WARNING! When F044 through F046 are used with 2-wire control, the starter may re-start automatically when time has expired. Adequate warnings similar to those in Section 3.1.3.b should be observed. Figure 5.6.6: Coast Down Lockout Timer F044 = Coast Down Lockout Timer (Back Spin Timer) Factory Setting = 0 (Disabled) Range = 1 - 60 minutes, or 0 (Disabled) F044 = 1 through 60 sets the number of minutes that the starter must be off before a restart can be attempted. This function is useful in applications such as pump motor backspin protection (where you need to prevent the pump motor from restarting if it is spinning backwards), 2 speed operations where speed changes require a minimum disconnect (spin-down timer), or reversing applications to prevent plugging (anti-plugging timer). F045 = Maximum Starts per Hour Lockout Factory Setting = 0 (Disabled) Range = 1 – 10 or 0 (Disabled) F045=1 through 10, will count the number of start commands within a 1 hour period. If the setting (maximum starts per hour) is exceeded, starting is prohibited until sufficient time has expired. This timer initiates upon the first start in an hour. It resets after 1 hour from that start and waits until another subsequent start to initiate again. (Often used in conjunction with F046). Note: Consult the motor manufacturer for a “Starts-per-Hour” or “Starting Duty Cycle” rating. Larger motors tend to have lower starts-per-hour ratings. 46