Download EMHEATER
Transcript
6.Detailed Function Description Code EM9 User's Manual Name Description Setting Range Factory setting 0.00~ F0.06 0.00~ F0.06 50.00Hz F8.13 FDT1 level (maximum frequency) F8.14 FDT1 lag 0.0~100.0%(FDT1 level) 0.0~100.0 5.0% These parameters set the detect level of output frequency and lag value of free output action. As shown in following diagram: Diagram 6-18 FDT level and lag diagram. Code Name Description Setting Range Factory setting Frequency arrive 0.0~100.0% F8.15 0.0~100.0 0.0% detecting range (maximum frequency) When output frequency reached the reference frequency, this function can adjust its detecting range. As shown in following diagram: Diagram 6-19 Frequency arriving signal diagram. Code Description Setting Range Factory setting 115.0~140.0% 115.0~140.0 130.0% (DC bus voltage) (380V series) F8.16 Brake threshold voltage 115.0~140.0% 115.0~140.0 120.0% (DC bus voltage) (220V series) This parameter is used to set the starting DC bus voltage of dynamic braking. Appropriate adjustments of this values can effective brake the load. 46 Name