EM9 User's Manual 6.Detailed Function Description Code Fb.09 Name Description Setting Range Protection time 0~65535h 0~65535h Input lack phase 0: Invalid Fb.10 0~1 protection selection 1: Valid Enter the lack phase three-phase power protection selection. 0: Invalid. When the input lack phase three-phase power, does not protect. 1: valid. Enter the lack phase three-phase power, the drive shows phase protection fault. Factory setting 0 1 FC Group--serial communication Code Name Description Setting Range Factory setting FC.00 Local address 0~247, 0: broadcast address 0~247 1 If the slave communication address in communication frame send by master is set to zero, that is the broadcast address, all slave on this MODBUS bus will receive this frame, but no response. And the slave address cannot set to zero. The local address is unique among its communication network; this is the base to realize point-to-point communication between master and inverter. Code Name Description Setting Range Factory setting 0: 1200BPS 1: 2400BPS 2: 4800BPS 0~5 3 FC.01 Baud rate selection 3: 9600BPS 4: 19200BPS 5: 38400BPS This parameter can set the data transmission rate during serial communication. The baud rate of master and slave must be the same, otherwise communication cannot establish. The larger baud rate we choice, the fast communicating speed we get. Code Name FC.02 Data format Description 0: No parity check (N, 8, 1) for RTU 1: Even parity check (E, 8, 1)for RTU 2: Odd parity check (O, 8, 1)for RTU 3: No parity check (N, 8, 2)for RTU 4: Even parity check (E, 8, 2)for RTU 5: Odd parity check (O, 8, 2)for RTU 6: No parity check (N, 7, 1)for ASCII 7: Even parity check (E, 7, 1)for ASCII Setting Range 0~17 Factory setting 0 57