Download Serial Code Prefix ABO & onwards
Transcript
INSTALLATION 19 Flue Terminal Position The terminal should be positioned so that products of combustion can safely disperse at all times. Pluming may occur at the termination so, where possible, terminal positions where this could cause a nuisance should be avoided. rf8392 Minimum dimensions are shown below m m 0 30 300mm in m min rf8393-1 625mm Fixed 300mm min Flat roof - with structure rf8394-1 A A A B 07 22 690mm Fixed 98 RF FLUE OUTLET Flat Roof Weather Collar Universal Weather Collar A = 600mm B = 2000mm The flue terminal shall not penetrate the shaded area of the roof Terminal Position Minimum Dimension Directly below an opening, air brick, windows, etc. 300 mm Below plastic / painted gutters 300 mm Painted surface 300 mm Below eaves or balcony 500 mm Below velux windows 2000mm Above or side of velux windows 600mm Note. The equivalent flue length resistance of the elbow kits are: 90o elbow kit = 1m 45o elbow kit = 0.6m Independent + Combi - Installation and Servicing