Download r USER MANUAL - E
Transcript
5) Make sure you cannot move the case within the cut out otherwise you do not have a NEMA 4X/IP65 protection. MOUNTING REQUIREMENTS Select a mounting location having the following characteristics: 1) it should be easy accessible also on the rear side. 2) there is no vibrations or impact 3) there are no corrosive gases (sulphuric gas, ammonia, etc.). 4) there are no water or other fluid (i.e. condense) 5) the ambient temperature is in accordance with the operative temperature of the instrument (from 0 to 50 °C). 6) the relative humidity is in accordance with the instrument specifications ( 20% to 85 % non condensing). The instrument can be mounted on a panel up to 15 mm thick with a square cutout of 45 x 92 mm. For outline and cutout dimensions refer to Fig. 2. The surface texture of the panel must be better than 6,3 µmm. The instrument is shipped with rubber panel gasket (50 to 60 Sh). To assure the IP65 and NEMA 4 protection, insert the panel gasket between the instrument and the panel as shown in fig. 1. screw bracket panel screw While holding the instrument against the panel proceed as follows: 1) insert the instrument through the panel gasket, 2) insert the instrument, with the panel gasket, through the panel cut out, 3) while pressing the instrument firmly against the panel, insert the mounting bracket and slide it up to the end of the case, 4) with a screwdriver, turn the screws with a torque between 0.3 and 0.4 Nm, gasket Fig. 1 GB 1