Transcript
WISE Sizing Engineering graphs s The specified sound levels dB(A) are applicable to rooms with an equivalent sound absorption area of 10 m2 (4 dB room attenuation). s The throw L0.2 is measured under isothermal discharge conditions. s Recommended max. permitted temperature below room temperature is 12 K. s All technical data applies to 360° distribution pattern. s For calculating the air stream propagation, air velocities in the occupancy zone, or sound levels in rooms with other dimensions, we refer to our ProAir Web calculation program. ProAir Web is available at www.swegon.com. Air flow – Pressure drop – Sound level – Throw s The diagrams should not be used for commissioning. s The dB(C) value is normally 6-9 dB higher than the dB(A) value. s Sizing example – size 160: – Given airflow 10-50 l/s at Pt 50 Pa. – Max. sound level 27 dB(A) – Throw = 2,0 m m in ADAPT C 160 40 dB(A) 1000 Sound data 35 500 400 Sound power level, Lw (dB) Table, Kok Size m ax pt Pa 30 300 25 200 20 Mid-frequency (Octave band) Hz 100 63 125 250 500 1000 2000 4000 8000 160 0 7 5 -2 -6 -10 -13 -7 250 1 5 2 -1 -3 -9 -12 -10 Tol. ± 2 2 2 2 2 2 2 2 50 40 30 20 3 4 5 10 20 Sound attenuation 'L Table 'L 125 250 500 1000 2000 4000 8000 160 15 9 9 20 19 15 16 14 250 13 8 10 19 16 13 16 16 Tol. ± 2 2 2 2 2 2 2 2 0,3 20 50 0,4 0,5 30 40 50 100 200 l/s 300 100 200 300 400 500 1 2 3 4 m3/h 5 10 l0,2 m ADAPT C 250 pt Pa 40 dB(A) 1000 m ax Mid-frequency (Octave band) Hz 63 40 m in Size 0,2 30 35 500 400 30 300 200 25 20 100 50 40 30 20 4 5 10 20 30 0,2 4 Swegon reserves the right to alter specifications. 20121114 20 40 0,3 50 0,4 0,5 30 40 100 50 200 1 100 300 2 200 3 4 300 l/s 400 1000 m3/h 400 500 5 www.swegon.com 10 l0,2 m