Download INSTALLER MANUAL
Transcript
INTEGRA Installer Manual 59 4. Wait until the LED goes off, then remove the jumper from pins – the control panel should automatically enter the service mode menu - the message “ÆEnd service” appears on the display of keypad with the lowest address number, and the SERVICE LED starts blinking. If the “Clear settings? 1=Yes” message appears on the main display, this means that the access to the service mode “with the use of jumpers” has been disabled in the control panel program (ÆService Mode ÆConfiguration ÆBlock SM). Then you can enter the service mode by pressing the number key 1, but this will erase all settings previously programmed in control panel (just like after performing functions mentioned in point 5 of this procedure). Having completed this operation, you may proceed to point 6. 5. Perform restart functions (ÆRestarts ÆClear settings / ÆClear codes / ÆClear event log). 6. Perform identification functions for modules connected (ÆStructure ÆHardware ÆIdentification ÆLCD keypads id. / ÆExpanders id.). Note: After identification, the addresses in keypads and expanders must not be changed. 7. Complete the service mode with “End service” function, saving data in FLASH memory. When the “Store settings in FLASH ? 1=Yes” prompt appears on the keypad display, press key with digit 1 – new settings will be saved and the control panel will enter the basic operation mode (waiting for code). 8. Call the service mode again. If the control panel re-enters the service mode, its operation is OK and you can proceed to further system installation (connection of expanders, detectors, sirens, keypads, etc.), as well as starting communication with the computer and programming all parameters required. Notes: • If the control panel is connected to a computer with running DLOADX program, the function of downloading via RS-232 will be started instead of the service mode. • Entering the service mode “with the use of jumpers” may be blocked with the “Block SM” function (function in “Configuration” position). Entering the service mode “with the use of jumpers” may be restored after acceptance of factory setting restoration. When exiting the service mode, the INTEGRA control panel checks whether the service programmable parameters have been changed. The „Wait...” message appears on the LCD display. If there are no changes in settings, the control panel prompts: “Store settings in FLASH ? 1=Yes” - after pressing the key [1] new settings will be saved in FLASH type memory. In large systems, the parameters which define the control panel operation are usually stored in the memory with independent battery backup. Disconnection of the memory power supply when the control panel is not supplied from the mains or 13.6V buffer power supply will erase the settings. Saving the data in FLASH memory prevents the erasure of settings and allows the control panel to restore them when an error is detected. Note: RAM memory errors should not occur, if the system is correctly configured and properly supplied.