1-72 Code ACH550-UH User’s Manual Name Range Resolution Default Group 22: ACCEL/DECEL 2201 ACC/DEC -6…7 1 0 (NOT SEL) 2202 ACCELER TIME 1/2 SEL 1 0.0…1800.0 s 0.1 s 30.0 s 2203 DECELER TIME 1 0.0…1800.0 s 0.1 s 30.0 s 2204 RAMP SHAPE 0.0…1000.0 s 0.1 s 0.0 s (LINEAR) 2205 ACCELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s 2206 DECELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s 2207 RAMP SHAPE 2208 EMERG DEC TIME 2209 RAMP INPUT 1 2 0 0.0…1000.0 s 0.1 s 0.0 s 0.0…1800.0 s 0.1 s 1.0 s -6…7 1 0 (NOT SEL) Group 23: SPEED CONTROL 2301 PROP GAIN 0.00…200.00 0.01 3.00 2302 INTEGRATION TIME 0.00…600.00 s 0.01 s 0.50 s 2303 DERIVATION TIME 0…10000 ms 1 ms 0 ms 2304 ACC COMPENSATION 0.00…600.00 s 0.01 s 0.00 s 2305 AUTOTUNE RUN 0, 1 1 0 (OFF) 0 (OFF) Group 25: CRITICAL SPEEDS 2501 CRIT SPEED SEL 0, 1 1 2502 CRIT SPEED 1 LO 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm 2503 CRIT SPEED 1 HI 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm 2504 CRIT SPEED 2 LO 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm 2505 CRIT SPEED 2 HI 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm 2506 CRIT SPEED 3 LO 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm 2507 CRIT SPEED 3 HI 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm Group 26: MOTOR CONTROL 2601 FLUX OPT ENABLE 0, 1 1 1 (ON) 2602 FLUX BRAKING 0, 1 1 0 (OFF) 2603 IR COMP VOLT 0.0…100.0 V 0.1 V 0.0 V 2604 IR COMP FREQ 0…100% 1% 80% 2605 U/F RATIO 1, 2 1 2 (SQUARED) 2606 SWITCHING FREQ 1, 2, 4, 8, 12 kHz - 4 kHz 2607 SWITCH FREQ CTRL 0, 1 1 1 (ON) 2608 SLIP COMP RATIO 0…200% 1% 0% 2609 NOISE SMOOTHING 0, 1 1 0 (DISABLE) 2619 DC STABILIZER 0, 1 1 0 (DISABLE) 0.1 kh 0.0 kh Group 29: MAINTENANCE TRIG 2901 COOLING FAN TRIG 0.0…6553.5 kh, 0.0 disables 2902 COOLING FAN ACT 0.0…6553.5 kh 0.1 kh 0.0 kh 2903 REVOLUTION TRIG 0…65535 Mrev, 0 disables 1 Mrev 0 Mrev 2904 REVOLUTION ACT 0…65535 Mrev 1 Mrev 0 Mrev 2905 RUN TIME TRIG 0.0…6553.5 kh, 0.0 disables 0.1 kh 0.0 kh 2906 RUN TIME ACT 0.0…6553.5 kh 0.1 kh 0.0 kh 2907 USER MWh TRIG 0.0…6553.5 MWh, 0.0 disables 0.1 MWh 0.0 MWh 2908 USER MWh ACT 0.0…6553.5 MWh 0.1 MWh 0.0 MWh Parameters User S
Related documents
ACH550-UH User`s Manual
ABB RDNA-01 User`s manual
User`s Manual - Culinaire Systems
1-130 ACH550-UH User`s Manual Parameters User
User`s Manual - Flow Tech, Inc.
ACS550-01/U1 Drive User's Manual
ABB ACH550 User`s manual
ACS550-01/U1 Drive User`s Manual
ACS310 User`s Manual - HSL Automation Home Page
Rion NL-27 User Manual
User`s manual ACB530
User`s Manual - HSL Automation Home Page