Download L-INX User Manual
Transcript
L-INX/L-GATE User Manual 2. 261 LOYTEC Proceed as described above to export the template in the Export M-Bus Device Template dialog. 10.7.7 Poll Groups In an M-Bus network, the master has to poll the slave devices. Input data points are therefore attached to a poll group. If nothing else is specified, the default poll group is used for input data points. The default poll group has a poll cycle of 60 seconds. Three different types of poll groups can be specified: Tip: Time-based: The poll group is triggered on a time base. This means that after a specific time – the poll cycle – the poll group is processed. Trigger-based: The poll group is triggered on a special trigger data point. As soon as the trigger condition is met, the poll group is processed. Trigger-based with synchronization: This type is similar to the trigger-based. The difference is that when the trigger condition is met, a broadcast synchronization message is sent over the M-Bus. This causes the devices which are able to perform a sync operation to store special data points for later reading. After the broadcast is sent, the poll group is processed. If an M-Bus device is only able to process default read requests, it is advisable to attach all data points of this device to the same poll group (this increases the performance). The poll group a data point is attached to can be changed in the properties view of the data points. The poll group can also be changed for multiple data points using multi-select. Version 4.4 LOYTEC electronics GmbH