Fire Detection Product Catalogue
Conventional (Non-Addressable) Detectors - Tyco 614 Series
614T Heat Detector
Tyco 614T heat detectors use a fast response,
thermistor based design. The fixed temperature
sensing thermistor readily tracks the local ambient
temperature, thus quickly, accurately and consistently
identifying when a fixed temperature is exceeded.
Rate-of-rise detection is achieved by comparing
the response of two thermistors, with one having a
slower thermal response. By combining accurate
thermistors with proper physical placement, this
patented rate-of-rise detection design achieves a high
level of heat detection performance.
Part Number
4098-9637EA
4098-9638EA
4098-9639EA
4098-9640EA
Model
614TA
614TB
614TC
614TD
Type
Type A
Type B
Type C
Type D
ActivFire
Listed
afp-1813
afp-1814
afp-1815
afp-1816
Specifications
Operating Voltage
Quiescent Current 1
Alarm Current 2
Alarm State Voltage 3
Remote Indicator
Relative Humidity
Ambient Temperature
Types A, B
Types C, D
Storage Temperature
Dimensions (mm)
Weight
11 to 32Vdc
85µA @ 24Vdc (typ.)
5mA to 80mA
3.0V to 12.4V
E500 Mk2 Series
10% to 95% (n/cond)
-10°C to +45°C
-10°C to +75°C
-20°C to +75°C
127 dia x 53H
174g with 5B base
1. Max. quiescent 110μA. 2. Min. 5mA for LED visibility; max.
current must be externally limited. 3. Min. voltage with remote
indicator shorted @ 5mA. Max @ 80mA without remote indicator
connected.
885WP-B IP67 Heat Detector
The 885WP-B is a 2 wire fixed temperature Type B
heat detector. This detector is designed to provide
open area protection in areas subject to moisture. It
is sealed against the entry of moisture to a rating of
IP67. The LED will latch on when the detector is in
alarm. Detectors are used with a mounting base that
permits mounting directly on to a 50mm or 60mm
junction box. The 885WP-B includes a tamperresistant feature that prevents its removal from the
mounting base without the use of a key. Flying leads
are provided for termination:- 2 Black (negative), 2
Red (positive), 2 White (positive Remote LED).
Specifications
Operating Voltage
Quiescent Current
Alarm Current (min.)
Alarm Current (max.)
Max. Air Velocity
Alarm Temperature
Ambient Temperature
Dimensions (mm)
Weight
Ingress Protection
ActivFire Listing
Part Number
The D515B Duct Sampling Unit consists of a
D51B duct housing fitted with a 5B base suitable
for fitting a non-addressable 614P photoelectric
smoke detector. The D51B is designed to sample
air in air conditioning ducts and pass the air through
the smoke detector. The housing is fixed on the
outside of the duct to be sampled, allowing easy
access for detector servicing and replacement of the
dust filter. To cater for most duct sizes, a sampling
tube extension is available in 3 metre lengths. Tyco
E500 Mk2 Series Remote Indicators can be used
for remote indication of an alarm. The D515B with
614P can be used with F3200 CIE logic for nonlatching operation. The D515B with Tyco 614P is
compatible with non-addresable alarm zone circuits
on VIGILANT and Simplex CIE.
Specifications
Duct Pressure*
Sampling Tube Length
Max. Duct Width
Remote Indicator
Dimensions
Base & Cover (LWH)
Fixed Tube Length
Sampling Tube Pitch
Duct Holes Required
Not ActivFire Listed
Part Numbers
D515B
D51COVER
D51L
D51F
D51T3
D51K100
8.5 to 30Vdc
< 50µA
2mA @ 3.1Vdc
80mA @ 6.5Vdc
20m/s
63°C (fixed temp.)
-15°C to +50°C
102 dia x 48H
170g with base
IP67
afp-1778
885WP-B
D515B Duct Sampling Unit
*AS 1603.13-1998 test
Page 8
www.tycofireprotectionproducts–anz.com
-1.15 to +3.0 kPa
160mm minimum
1.8m
E500 Mk2 Series
278x190x113 mm
160 mm below base
122mm
24mm dia. x 2 places
D51 c/w 5B base**
D51 Cover only c/w screws
Baffle box of 10
Filter box of 10
3m Sampling Tube
Sampling Tube End Cap
pkt of 10
**Wired for collective base