Table 1.6 Parameter Description ( continued 3/7 ) Contained Basic Parameter Display Function Notation Format in IN1 IN1U DP1 Parameter Description IN1 Sensor Type Selection IN1 Unit Selection IN1 Decimal Point Selection Setup Menu 7 8 9 10 11 12 13 14 15 16 17 0 1 2 0 1 2 3 : : : : : : : : : : : : : : : : : : N type thermocouple L type thermocouple PT 100 ohms DIN curve PT 100 ohms JIS curve 4 - 20 mA linear current input 0 - 20 mA linear current input 0 - 1V linear Voltage input 0 - 5V linear Voltage input 1 - 5V linear Voltage input 0 - 10V linear Voltage input Special defined sensor curve Degree C unit Degree F unit Process unit No decimal point 1 decimal digit 2 decimal digits 3 decimal digits Default Value 1 ( 0 ) 0 (1) 1 IN1L IN1 Low Scale Value Low: -19999 High: 45536 0 IN1H IN1 High Scale Value Low: -19999 High: 45536 1000 IN2 IN2 Signal Type Selection 0 1 4 5 6 7 20 : : : : : : : IN2 no function Current transformer input 0 - 1V linear voltage input 0 - 5V linear voltage input 1 - 5V linear voltage input 0 - 10V linear voltage input Perform Event input function 1 IN2U IN2 Unit Selection Same as IN1U 2 DP2 IN2 Decimal Point Selection Same as DP1 1 IN2L IN2 Low Scale Value Low: -19999 High: 45536 0 IN2H IN2 High Scale Value Low: -19999 High: 45536 1000 OUT1 Output 1 Function O1TY 10 Range Output 1 Signal Type UM25001C 0 1 0 1 2 3 : : : : : : Reverse (heating ) control action Direct (cooling) control action Relay output Solid state relay drive output Solid state relay output 4 - 20 mA current module 0 0