TCM 330 / TCM 330U LED CONTROLLER MODULE
5.2
Factory-configurable parameters
Certain parameters that are critical for correct operation can only be modified during factory production using a dedicated programmer to access the configuration area of TCM 330.
These parameters cannot be modified during normal operation using remote commissioning
(see chapter 5.3) or the local configuration interface (see chapter 5.1).
These parameters are listed in the table below.
Parameter
Relay Utilized
Relay Switch On Time
Relay Switch Off Time
Relay Overdrive Active Time
Default Value
True
4.6ms
1.5ms
110ms
Note
50us steps
50us steps
Active only on OFF to ON transition
Please contact EnOcean for support if modification of these parameters is required.