Download User Manual

Transcript
USER MANUAL V1.0
TCM 330 / TCM 330U LED CONTROLLER MODULE
Parameter
Description
Default Value
Comment
Generic Sensor Parameters (Occupancy and Light Level)
SensorRampUpSpeed
SensorRampDownSpeed
Ramp-up speed when change is triggered by an occupancy or
light level sensor (2 point mode)
Ramp-down speed when change is triggered by an occupancy or
light level sensor (2 point mode)
20%/s
20%/s
0= No ramp
(immediate)
0= No ramp
(immediate)
System Parameters
MinVoltageLevel
Minimum 0-10V output voltage level when light is switched ON
1.0V
MaxVoltageLevel
Maximum 0-10V output voltage level when light is switched ON
10.0V
0-10VRelayDelay
Delay between switching the relay on and starting to ramp up
the 0-10V output
50ms
ModeAfter-PowerLoss
ModeAfterPowerLoss (ON/OFF/LAST STATE)
LAST STATE
StatusMessageTimer
Defines, how often status messages are transmitted (seconds)
0xFFFF
RepeaterFunction
Defines the repeater level of the device (OFF/1-Level/2-Level)
OFF (disabled)
RepeatLinkedDevicesOnly
Configures the repeater to only repeat telegrams from devices linked
ON (enabled)
to it
EnableDebugMessages
Enable or disable debug messages
EnableLinkChecker
Enable or disable link checker
(If a learn telegram from a linked device is received while in operating ON (enabled)
mode, the 0-10V output will toggle once between 10% and 90%)
© 2015 EnOcean | www.enocean.com
TCM 330 User Manual | v1.0 | September 2015 | Page 50/62
OFF (disabled)
Applies only
to LEDR
0=OFF
0xFFFF=only
event based