14 Configuration sheets
14.1 Normal operation
DIP
DIP
DIP
Function
1
off
on
off
on
off
on
off
on
2
off
off
on
on
off
off
on
on
3
off
off
off
off
on
on
on
on
Light Type (Note 1)
MI-20KW-A
MI-20KWD-A
MI-20KW-A + OPT-IR-20KW-A
MI-20KWD-A + OPT-IR-20KWD-A
HI-50KW-A
HI-50KWD-A
HI-50KW-A + OPT-IR-50KW-A
HI-50KWD-A + OPT-IR-50KWD-A
4
off
on
off
on
5
off
off
on
on
Flash rate (Note 2)
20 fpm
30 fpm
40 fpm
60 fpm
6
off
on
Night mode operation (Note 3)
Red and infrared LEDs flashing
Red and infrared LEDs in steady-burning mode
7
off
on
Test mode enable
Normal operation
Test mode enabled (see Test mode chart for DIP switch settings)
8
off
on
Master/Slave mode
This device is slave
This device is master
9
Reserved
10
off
on
RS-485 termination
Termination resistor on controller board unconnected.
120Ω bus termination resistor on controller board connected to RS-485 bus.
Remarks
Note 1
Note 2
Note 3
Various operating voltages are omitted here for clarity.
Customer-specific flash rates available.
Applicable to models with suitable hardware and required options installed.