AKD Installation | 6 Technical description and data
6.17.4 Safety instructions
Drives with a suspended load must have an additional safe mechanical blocking
(for instance, by a motor-holding brake). The drive cannot hold the load when STO
is active. Serious injury could result when load is not properly blocked.
If the safety function STO is automatically activated by a control system, then make
sure that the output of the control is monitored for possible malfunction. The monitoring can be used to prevent a faulty output from unintentionally activating the
STO function. Since the STO function is a single-channel system, erroneous engaging will not be recognized.
It is not possible to perform a controlled brake if the drive controlled STO-Enable is
off. If controlled braking before the use of the STO function is necessary, the drive
must be braked and the input STO must be separated time-delayed from +24 V .
The STO function does not provide an electrical separation from the power output.
If access to the motor power terminals is necessary, the drive must be disconnected from mains supply considering the discharging time of the intermediate
circuit. There is a danger of electrical shock and personnel injury.
Use the following functional sequence when the STO function is used:
1. Brake the drive in a controlled manner (speed setpoint = 0 V).
2. When speed = 0 rpm, disable the drive (enable = 0 V).
3. If a suspended load is present, block the drive mechanically.
4. Activate the STO function.
6.17.5 Technical data and pinning
Pin
1
2
3
Signal
+24
GND
STO
Description
+24 Vdc Auxiliary voltage
24V Supply GND
STO enable (Safe Torque Off)
6.17.6 Enclosure
Since the drive meets IP20, you must select an enclosure that permits safe operation of the drive. The enclosure
must at least meet IP54 .
6.17.7 Wiring
If you are wiring leads that are outside the specified enclosure (IP54), the cables must be laid durably (firmly), protected from outside damage (for example, by laying the cable in a duct), placed in different sheathed cables, or
protected individually by grounding connection.
Wiring remaining within the specified enclosure must meet the requirements of the standard IEC 60204-1.
54