Specifications
Preventa™ safety PLCs
Modular, XPSMF60
Rack, power supply and CPU
Environment
Modular safety PLC
2
Rack XPSMFGEH01 + power supply module XPSMFPS01 and central
processing unit XPSMFCPU22
Products designed for max. use in safety related parts of
control systems (conforming to EN 954-1, EN/ISO 13849-1 and
EN/IEC 61508)
Category 4 (EN 954-1),
Performance level “e” (EN/ISO 13849-1),
Safety integrity level: SIL 3 (EN/IEC 61508)
Product certifications
EN/IEC 61508, part 1-7: 2000, IEC 61511 part 1-3: 2004, DIN VDE 0116: 1989,
EN 50156-1: 2004, EN 12067-2: 2004, EN 298: 2003, EN 230: 1990,
NFPA 85: 2001, EN/IEC 61131-2: 2003, EN 61000-6-2: 2001, EN 61000-6-4: 2001
EN 54-2: 1997, NFPA 72: 2002
Ambient air temperature
conforming to EN 61131-2
Operating
°F (°C)
Rack, power supply module and CPU: +32… + 140 (0…+ 60)
Storage
°F (°C)
bb Rack XPSMFGEH01: -40… + 185 (- 40…+ 85),
bb Power supply module XPSMFPS01:
vv -40… + 185 (- 40…+ 85), without backup battery
vv -22… + 185 (- 30…+ 85), with backup battery
bb Central processing unit XPSMFCPU22: -40… + 185 (- 40…+ 85)
Relative humidity
Degree of protection
95% (supply not connected)
Enclosure
IP 20 with covering plate on unused “in rack” I/O card slots
Pollution
Degree of pollution II
Altitude
6560 ft (2000 m)
Protection class
Class II, conforming to EN/IEC 61131-2
Electromagnetic compatibility
Conforming to EN/IEC 61131-2
Vibration resistance
conforming to EN 61131-2
Operating
1 g, frequency 10…150 Hz, unit test while operating, 10 cycles per axis
Shock resistance
conforming to EN 61131-2
Operating
15 g (duration 11 ms), unit test while operating, 2 cycles per axis
Resistance to electrostatic discharges
conforming to EN/IEC 61000-4-2
kV
4 contact, 8 air discharge
Immunity to high frequency interference
conforming to EN/IEC 61000-4-3
V/m
10 (26 MHz…1 GHz)
Rack material
Metal alloy
Electrical specifications
Supply
Voltage
V
Voltage limits
Output voltage of power supply module
c 24 (External supply with separate protection conforming to EN/IEC 60950, SELV
(Safety Extra Low Voltage) or PELV (Protection Extra Low Voltage) rated)
- 15… + 20% (power supply module)
- 20… + 25%
V
c 3.3 / 10 A
V
c 5 / 2A
Maximum power consumption
A
30 max., 32 A external fuse
Immunity to momentary supply interruptions
ms
10
ms
Depending on size of application
Protection
Internal fuse
Response time
Backup capacitor
Approximately 1 week for diagnostics and time information
Program is not effected
Clock
Yes
Operational data of CPU
c 3.3 V/1.5 A
c 5 V/1 A
User memory
Application
kB
500
Data
kB
500
LED display
Yes
Communication
Ethernet network: safety communication using SafeEthernet protocol
Compatibility
Transmission
Central processing unit XPSMFCPU22
Communication ports
Baud rate
Structure
Introduction:
page 2/38
2/46
100 Half duplex, 10 Full duplex, Autonegotiation
10BASE-T/100BASE-TX
Medium
Functions
Integrated 4 RJ45 switched Ethernet communications ports
Mbps
Dual twisted pair cable, category 5D or better (Ethernet)
Control of:
Transmitted data: duplication, loss, bit changing.
Addressing of transmitted and received messages.
Data sequence: repetition, loss of data, change. Data reception time: delay, repetition, echo
Diagnostics on:
CPU, user program, communication, operating voltage and temperature, inputs & outputs
Specifications:
page 2/46
References:
page 2/48
Dimensions, mounting:
page 2/52
Connections:
page 2/53