To program the unit for Example 1 Level Monitoring with alarms by
using the Quick Setup menu proceed as follows.
If required access the Program Mode
Key in the passcode 1997 and press ENTER
Using the ‘right’ arrow key go to the Quick Setup menu press ENTER and
as prompted, by the questions, select the relevant option and ENTER.
Question
Level, Pump Up/Down or
Differential
No. of Alarms
Type Alarm 1
Alarm No 1
Type Alarm 2
Alarm No 2
Xducer (P101)
Material (P102)
Measnt Units (P104)
Empty Level (P105)
Span (P106)
Option
1 = Level App.
2 = 2 Alarms
1 = High
1 = Set Relay 1
2 = Low
2 = Set Relay 2
2 = dB6
1 = Liquid
1 = metres
3.5 (metres)
2.8 (metres)
Programming is now complete and the unit can be returned to the run mode,
press CANCEL until Run Mode? Is displayed on the LCD press ENTER,
and the Advanced 120 will return to the Run Mode.
Note
If relay setpoints do not meet the exact requirements of the application, they
can be modified to suit by pressing ENTER when, “For More Options Hit
Enter”, is displayed and entering new values to relay setpoints as required.
Alternatively the relevant relay setpoint can be accessed either by the main
menu system or directly via parameter number and changed as necessary.
Page 74