Download ULTRA 5 - Ventim
Transcript
P101 Xducer (Transducer) This parameter should be set to the transducer being used with the unit, and can be set to one of the following: Option Description When Ultra Wizard = 1 Level/Vol. or 2 Pump/Diff. 0=Auxiliary Use the optional mA input (Please consult Pulsar (Optional) for availability). 1 = dB3 Transducer is a dB3. Range 0.125 to 3.00 metres 2 = dB6 (Default) Transducer is a dB6. Range 0.3 to 6.00 metres 3= dB10 Transducer is a dB10. Range 0.3 to 10.00 metres 4= dB15 Transducer is a dB15. Range 0.5 to 15.00 metres 5= dB25 Transducer is a dB25. Range 0.6 to 25.00 metres 6 = dB40 Transducer is a dB40. Range 1.2 to 40.00 metres 7 = dBS6 Transducer is a dBS6. Range 0.2 to 6.00 metres 8 = dBMach3 Transducer is a dBMach3 Range 0.0 to 2.425 mtrs. When Ultra Wizard = 3 Flow 0=Auxiliary Use the optional mA input (Please consult Pulsar (Optional) for availability). Transducer is a dBMach3 Range 0.0 to 2.425 mtrs. 1 = dBMach3 (Default) 2 = dB6 Transducer is a dB6. Range 0.3 to 6.00 metres 3= dB10 Transducer is a dB10. Range 0.3 to 10.00 metres 4= dB15 Transducer is a dB15. Range 0.5 to 15.00 metres 7 = dBS6 Transducer is a dBS6. Range 0.2 to 6.00 metres P102 Material This parameter should be set to the type of material being monitored. Option 1 = Liquid (Default) 2 = Solid Page 140 Description Use for liquids and flat solid materials Solid material that is heaped or at an angle