Download - Spectrum Controls, Inc.
Transcript
50 Compact IO™ Universal Input module Determining Effective Resolution and Range The effective resolution for an input channel depends upon the filter frequency selected for that channel. The following tables provide the effective resolution for each of the range selections at the six available frequencies. The tables do not include the affects of unfiltered input noise. Choose the frequency that most closely matches your requirements. Table 4.6a Effective Resolution(In counts) vs. Input Filter Selection Raw/Proportional Counts Input Type 60Hz 50Hz 10Hz 250Hz 4to20mA 1 2 1 8 0to20mA 1 1 1 12 -10V to +10V 0 0 0 3 0to10V 1 0 1 2 1to5V 1 1 0 3 0to5V 1 1 0 5 -100mV to +100mV 1 1 1 14 -50mV to +50mV 2 1 1 13 Type J-TC 4 4 2 35 Type K-TC 12 7 6 58 Type T-TC 63 72 41 548 Type E-TC 8 8 5 34 Type R-TC 14 18 11 120 Type S-TC 17 16 6 112 Type B-TC 31 28 17 175 Type N-TC 5 7 3 39 Type C-TC 6 6 3 60 100 Pt 385 3 2 1 17 200 Pt 385 1 0 1 7 500 Pt 385 1 0 0 3 1000 Pt 385 1 1 0 3 100 Pt 3916 3 2 1 26 200 Pt 3916 1 2 1 12 500 Pt 3916 1 1 0 6 1000 Pt 3916 0 1 0 7 10 Cu 426 50 40 14 149 120 Ni 618 2 3 1 30 120 Ni 672 2 2 1 23 604 NiFe 518 1 1 0 10 150 ohm 5 5 2 20 1000 ohm 1 2 1 7 3000 ohm 1 0 0 10 Note: A 1000 samples were taken to find the deviations listed above. 500Hz 33 33 6 16 21 16 40 46 71 162 863 123 365 381 805 102 162 51 16 57 10 21 20 83 24 206 21 27 35 107 39 21 1000Hz 201 268 48 96 80 65 160 61 209 761 2036 625 1104 928 1633 319 341 408 93 514 332 684 156 453 63 1647 518 261 631 1372 102 68