Installation Guide and Operating Manual 4.6.2 False Alarm Immunity The following tables represent the minimum distance at which the Detector did not false alarm or show any signs of instability during exposure to the sources listed below. Additionally, the sensitivity to a one (1) square foot n-Heptane reference pan fire in the presence of the false fire source is listed. Minimum Distance with no Alarm Sensitivity to a 1' x 1' n-Heptane reference pan fire in the presence of the false fire source Direct Sunlight No Alarm 50 feet /15.24 meters Modulated Sunlight No Alarm 25 feet / 7.62 meters Modulated Arcwelding 3 feet 9 inches / 1.14 meters Source at 15 feet / 4.57 meters Fire at 30 feet / 9.14 meters Continuous Arcwelding 3 feet 9 inches / 1.14 meters Source at 15 feet / 4.57 meters Fire at 30 feet / 9.14 meters Resistive Electric Heater 1 foot / 30.48 centimeters Source at 3 feet / 91.44 centimeters Fire at 200 feet / 60.96 meters Flourescent Lamp 1 foot / 30.48 centimeters Source at 3 feet / 91.44 centimeters Fire at 200 feet / 60.96 meters Halogen Lamp 1 foot / 30.48 centimeters Source at 7 feet / 2.13 meters Fire at 200 feet / 60.96 meters Sodium Vapor Lamp 1 foot / 30.48 centimeters Source at 3 feet / 91.44 centimeters Fire at 200 feet / 60.96 meters Pelican Flashlight 1 foot / 30.48 centimeters Source at 3 feet / 91.44 centimeters Fire at 200 feet / 60.96 meters Incandescent Lamp 1 foot / 30.48 centimeters Source at 3 feet / 91.44 centimeters Fire at 200 feet / 60.96 meters False Fire Source Honeywell 21