Download - Schneider Electric

Transcript
Section 9: Communication
Communication ports
Remote port X5
Physical interface
The physical interface of this port depends of the communication
letter in the order code. See Figure 9.1, the section Rear panel
connector X5 (REMOTE), and the table below. The TTL interface is
for external converters and converter cables only. It is not suitable
for direct connection to distances more than one meter.
Physical interface and connector types of remote port X5 with various options. TTL (A) is the default.
Order Code
A
B
C
D
E
F
G
63230-218-205
Communication Interface
TTL (for external converters only)
Plastic fiber interface
Not available
RS-485 (isolated)
Glass fiber interface (62.5/125 µm)
Plastic Rx/glass (62.5/125 µm) Tx fiber interface
Glass (62.5/125 µm) Rx/plastic fiber interface
© 2015 Schneider Electric. All rights reserved.
Connector Type
D9S
HFBR-0500
screw crimp
SMA
HFBR-0500/SMA
SMA/HFBR-0500
261