Remark ● Setting example for the control to rise the temperature by 200 for 40 minutes It takes approx. 24 seconds to rise the temperature by 2. Also, the dead time of the controlled object must be added as the time required before the temperature starts rising. Therefore, when assuming the dead time of the controlled object is 6 seconds, set 30 (24 seconds + dead time of the controlled object) to CH Loop disconnection detection judgment time (Un\G59, Un\G91, Un\G123, Un\G155). (3) When an alert occurs, or does not occur If an alert for the loop disconnection detection occurs, CH Alert occurrence flag (XnC to XnF) and CH Loop disconnection detection (b13 of Un\G5 to Un\G8) turn on and Alarm code (03oAH) is stored in Error code (Un\G0). ( Page 319, Section 11.7) If an alert for the loop disconnection detection does not occur and auto tuning is normally completed, the value in CH Loop disconnection detection judgment time (Un\G59, Un\G91, Un\G123, Un\G155) is automatically updated to the value calculated by auto tuning. There is a possibility of an error in the control loop if the loop disconnection alert occurs. For this reason, even when auto tuning is normally completed, check the control loop and examine the appropriateness of the loop disconnection detection judgment time during auto tuning. (4) To clear the alert status If any of the following conditions is met, CH Alert occurrence flag (XnC to XnF) and CH Loop disconnection detection (b13 of Un\G5 to Un\G8) turn off. • CH PID control forced stop instruction (YnC to YnF) is turned on from off. • Setting/operation mode instruction (Yn1) is turned off from on and the mode has shifted to the setting mode. • A manipulated value (MV) becomes greater than the lower limit output limiter value and smaller than the upper limit output limiter value. • Disable (0) is set to During AT loop disconnection detection function enable/disable setting (Un\G571). • 0 is set to CH Loop disconnection detection judgment time (Un\G59, Un\G91, Un\G123, Un\G155). • MAN (1) is set to CH AUTO/MAN mode shift (Un\G50, Un\G82, Un\G114, Un\G146). After performing the operations above, turn on and off Error reset instruction (Yn2) to clear the value in Error code (Un\G0). 204
Related documents
MELSEC-Q Temperature Control Module User`s Manual
BAHNER-THESIS-2015 - OAKTrust Home
MELSEC-Q Temperature Control Module User's Manual
CNC Code Shooter Help File
Programmable Logic Controllers L Series
PSU Climate Champions Guidance Document
6000i CNC User`s Manual - Acu-Rite
User manual (GB)
User Manual - Pid Controller
QCRTGraph CF Real-Time Graphics Tools for the - Quinn
INSTALLATION AND SAFETY MANUAL
Application Handbook - Applied Biological Materials