User Manual
RS 232 Firmware
2.3.2 M12 connector with fixing bush (Optional)
WARNING
For work carried out in hazardous areas, special regulations (Standard EN 60079-14 and EN 6007917) must be observed.
Work at the open actuator under voltage must only be performed if it is assured that for the duration of
the work there is no danger of explosion.
Pay attention to additional national regulations.
Only remove electrical connections when disconnected from the mains.
Wait at least two minutes after disconnecting the voltage supply and unplugging the plug/socket
connectors before opening the drive.
The connections X2 to X8 are made with M12 connectors. The
enclosure protection indicated on the name plate is onlx ensured,
if connectors are connected to all sockets or temporary covers
are fitted and fastened with the specific torque and if the
enclosed fixing bushes have been mounted properly.
• Check whether type of current, supply voltage and
frequency correspond to motor data (refer to name
plate at motor).
• Loosen screws and remove fixing bush (refer to figure
2.3.7)
Figure 2.3.7: fixing bush for M12
Attention: The screws in the cover are not secured against
falling out. When opening the cover, ensure that no screws are
lost!
• Slip fixing bush onto the cable (refer to figure 2.3.8).
The diameter of the M12 connector must be 16mm
maximum.
• Fit M12 connector and fasten it tightly.
• Set the fixing bush in position and tighten it with
screws (refer to figure 2.3.9).
Attention: Set the fixing bush with the three screw holes
showing to the outer side of the MDA (refer to figure 2.3.9).
Figure 2.3.8: slipping the fixing bush
• Connect cables according to the order-related wiring diagram.
The actuator must only be set under voltage, if connectors are
connected to all sockets or temporary covers are fitted and fastened
with the specific torque and if the enclosed fixing bushes have been
mounted properly.
Figure23.3.9: tightening fixing bush