Chapter 2. MOUNTING AND WIRING ■ Wiring the solenoid valve CAUTION Do not connect the solenoid valve to the voltage side. If a ground fault occurs, ground current will flow to the solenoid valve and open it, causing fuel to flow regardless of the state of this control. ● Correct connection 100V Ground side (G) N (Ground fault) L Burner Power Flame relay FRS100 Valve (closed) Combustion unit Voltage side (H) Fuel Ground current will not flow to the solenoid valve if the valve is wired as shown in the figure above, even if faulty insulation on the voltage side (H) causes a ground fault. Accordingly, the valve will not open, eliminating the risk of fuel discharge. ● Wrong connection (Ground fault) 100V Burner Power Flame relay FRS100 Ground side (G) N L Valve (open) Combustion unit Voltage side (H) Fuel Ground current will flow to the solenoid valve if the valve is wired as shown in the figure above and if a ground fault occurs. Accordingly, the solenoid valve will open regardless of the flame relay, causing fuel discharge. 2-7