Download Phoenix Interface - Johnson Controls | Product Information
Transcript
If your readings are within these values, go on to Step 5. HRD GND N2 Bus Terminal Block on ASC NCU 6 3 SFT GRD 5 SFT GRD 2 N2(-) ZBus REF N2+ to REF +2.45 to 2.98 VDC N2- to REF +2.06 to 2.54 VDC N2 + 4 1 N2(+) N2AREF N2 - DMM N2+ to N2+0.36 to 0.92 VDC DMM Note: For best reading, place probe on metal plate inside terminal, not on screw. VOLTAGE2 Figure 23: Measuring N2 Voltages at PHX 5. Before connecting the three N2 Bus wires to the PHX, identify the correct voltage and polarity of each wire with the DMM. The voltages should match the following: N2+ to REF = +2.45 to 2.98 VDC N2- to REF = +2.06 to 2.54 VDC REF to earth ground = ≤1.0 VDC/VAC, referenced to earth ground with 100K ohm resistor across the DMM If the voltages are not within the above ranges, end-of-line termination may not be set correctly. Locate and fix the problem. 6. Connect the N2 Bus wires to the PHX and continue to the next PHX. Perform Steps 4 and 5 until you have connected each PHX to the N2 Bus. These steps comprise the simplest and most thorough N2 Bus test. 3-42 Laboratory Controls––Phoenix Interface