Download Phoenix Interface - Johnson Controls | Product Information
Transcript
Makeup Air Controller Terminal Points The MIJ400 Makeup Air Controller terminal points are located on terminal block TB4. The MIJ500 Makeup Air Controller terminal points are located on terminal block TB9. Table 8: Makeup Air Controller Terminal Points Pin * Description 1 +15V 2 GND 3 -15V 4 Flow Command 5 Scaleable Flow Feedback 6 Flow Alarm 7* Scaleable Flow Command 8* Open These connections are only available on the MIJ500. Ancillary Terminal Points The MIJ500 Ancillary terminal points are located on terminal block TB11. Note: The MIJ400 does not have these points. Table 9: Auxiliary Terminal Points Pin Description 1 +12V 2 Emergency Override Input 3 Switched Flow Quantity 4 Hot Deck/TAC Command 5 Hot Deck/Flow Feedback 6 Hot Deck Alarm Laboratory Controls––Phoenix Interface 3-21