AEFR
SAFETY PRECAUTION This manual uses the following symbols to ensure safe operation of this product.
DIGTAL FREQUENCY RELAY
User's Manual
WARNING
CAUTION
Warnings are indicated when mishandling this product might result in death or serious injury
to user.
Cautions are indicated when mishandling this product might result in minor injury to the user,
or only physical damage to the timer.
WARNING
RESTRICTIONS ON USE
When using this product in applications
that require particular safety or when
using this product in important facilities,
please pay attention to the safety of the
overall system and equipment. Install failsafe mechanisms, perform redundancy
checks and periodic inspections and
adopt other appropriate safety measures
when it is necessary.
ΘNote this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
been correctly wired before turning the power ON.
ΘBefore wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
electric shock.
ΘDo not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
ΘDo not disassemble the product. Doing so might cause electric shock or faulty operation.
CAUTION
ΘUse the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
ΘMake sure the product is firmly connected to the socket. Failure to do so might cause electric shock or fire.
SPECIFICATIONS
NAMES AND FUNCTIONS OF FACEPLATE
Frequency indicator
Display
Operating voltage
AC : 100 ~ 240V
Allowable operating
voltage range
85 ~ 110% of rated operating voltage
Rated frequency
50 / 60 Hz
Time indicator in second
Relay output indicator
ON
Contact rating
250VAC 5A (Resistive load)
Display
Display resolution ²0.1Hz
Power consumption
Approx. 3VA
Life
Mechanical : 5,000,000 times / Electrical : 100,000 times
Under frequency setting
ANLY
-10 ~ +50 °C
Ambient humidity
MAX 85% RH
Weight
Approx. 130g
Reset delay time
TYPE AEFR
OVER UNDER RESET ERROR
FREQ. FREQ. TIME
TIME
Over frequency setting
Ambient temperature
Hz
S
UNDER
OVER
Setting values display
OFF
TEST
Error delay time
AUTO RESET
Manual reset
RESET
Function settings
SETTING PROCEDURE
1. Over frequency setting
3. Auto reset time setting
Hz
ON
S
S
2. Under frequency setting
ON
OVER
UNDER
Hz
ON
UNDER
FREQ.
S
ERROR
TIME
Set the delay time for error.
The display will show existing
frequency after 3 seconds.
Set the desired value for under
frequency. The display will show
existing frequency after 3 seconds.
ON Over frequency enable
Hz
ON
ON Under frequency enable
Hz
S
OFF Under frequency disable
ON
Hz
S
AUTO
ON Auto reset
RESET
OFF Manual reset
ON
Hz
S
OVER FREQUENCY
SETTING VALUE
UNDER FREQUENCY
SETTING VALUE
RESET TIME
ERROR TIME
CONNECTION
2. The fault indications
The existing frequency
will be shown as follow.
ON
Hz
S
OFF Over frequency disable
DISPLAY
1. Frequency display
By pressing "TEST" button, all setting value
will be shown ordinally as follows. The display
will show existing frequency after 3 seconds.
AUTO RESET
OFF
4. Error delay time setting
Hz
S
UNDER
OVER
RESET
TIME
Set the delay time for auto reset.
The display will show existing
frequency after 3 seconds.
Set the desired value for over
frequency. The display will show
existing frequency after 3 seconds.
ON
Hz
ON
OVER
FREQ.
6. Setting values display
5. The function of DIP switches
OVER FREQUENCY
4
Hz
ON
S
3
UNDER FREQUENCY
2
S
6
7
1
Hz
ON
5
8
S
NO INPUT
SOURCE
Hz
ON
AC 100 ~ 240V
S
TIMING CHART
Rt
Et
Rt
Et
Rt
OVER FREQUENCY
SO URCE
UNDER FREQUENCY
N. O . ( 1- 3)
N. C. ( 1- 4)
Rt : Reset Time
Et : Error Time
ANLY ELECTRONICS CO., LTD.
http://www.anly.com.tw
M-AEFR-B-E
Printed in Taiwan