Variable Speed Drive (P_VSD)
Table 18 - Engineering Tab Page 2 Descriptions
Function
Action
Security
Configuration Parameters
Drive has Run
Feedback
Check if the drive provides a run
feedback signal. This enables feedback
checking for Fail to Start and Fail to
Stop.
Clear this checkbox if there is no run
feedback.
IMPORTANT: Checking this places the
device in Maintenance Bypass unless
'Use Run Feedback' on page 1 of the
Maintenance tab is checked.
(See Maintenance Tab on page 49.)
Engineering
Configuration
(Code E)
Cfg_HasRunFdbk
Drive has Speed
Feedback
Check if the drive provides speed
feedback on Inp_SpeedFdbk.
IMPORTANT: Checking this option
enables the next configuration setting
and the Output Datalink Limits on page
2 of the Maintenance tab.
(See Maintenance Tab Page 2 on
page 51.)
Engineering
Configuration
(Code E)
Cfg_HasSpeedFdbk
Use Speed Feedback
>0 to imply running if
Run Feedback is not
used
Check if Speed feedback greater than
zero is used to signify the drive is
running.
IMPORTANT: This configuration
setting is available only if the previous
configuration setting is checked.
Cfg_UseSpeedFdbk
Clear Program
Commands on Receipt
Check to have the P_VSD instruction
clear Program commands (PCmd) as
soon as they are received (default).
Cfg_PCmdClear
Operator command
resets fault
Check to have a new operator drive
command reset faults.
Clear this checkbox for ‘reset required’
to clear fault.
Cfg_OCmdResets
Mode Configuration Display
This display lets you select the default mode for the object by selecting the
appropriate mode.
IMPORTANT
If no mode is being requested, changing the default mode changes the mode
of the instruction.
You must have FactoryTalk View security code E to select the default mode on
this display.
Rockwell Automation Publication SYSLIB-RM016E-EN-E - August 2014