Download syslib-rm016 - Literature Library
Transcript
Variable Speed Drive (P_VSD) Execution The following table explains the handling of instruction execution conditions. Condition Description EnableIn False (false rung) Processing for EnableIn False (false rung) is handled the same as if the drive were disabled by command. The drive outputs are de-energized and the drive is shown as disabled on the HMI. Powerup (prescan, first scan) Processing of modes and alarms on prescan and powerup is handled by the embedded P_Mode and P_Alarm AddOn Instructions - refer to their specifications for details. On powerup, the drive is treated as if it had been commanded to stop. Postscan (SFC transition) No SFC postscan logic is provided. Refer to the Logix5000™ Controllers Add-On Instructions Programming Manual, publication 1756-PM010, for more information. 32 Rockwell Automation Publication SYSLIB-RM016E-EN-E - August 2014