Download 7300EV Manual
Transcript
Chapter 5 Trouble shooting and maintenance 3. Errors which can only be recovered manually but cannot be auto-recovered Display OC OL1 OL2 OCL LVC Error Over-current during stop Motor overload Cause 1. Detection circuit malfunctions 2. Bad connection for CT signal cable Send the inverter back for repair 1. Increase motor capacity 1. Heavy load 2. Improper settings of F43 Inverter overload Heavy load Over current limit Remedy 2. Set F43 correctly according to motor nameplate. Increase inverter capacity 1. Heavy Load 1. Increase motor capacity 2. Continuous over load 2.Increase ACC/ DEC time F02~F03 3.set stall prevention function C1~C6 1. Power voltage too low Under voltage 2. Power voltage varies during operation widely 1.Improve power quality. 2.Set a longer acceleration time 3. Add a reactor at the power input side 4. Increase inverter capacitor Note: 〝@ 〞means when the inverter broken ,the failure contact does not action. 5-3