Download SDC15 Single Loop Controller User`s Manual for
Transcript
Chapter 5. SETTINGS BEFORE STARTING OPERATION ■ Control action (Direct/Reverse) setup (1) In the operation display mode, keep the [para] key pressed for 2 sec. or longer. >> The unit then enters the parameter setting mode. pv sp mode rdy man ev1 ev2 ev3 ot1 ot2 man ev1 ev2 ev3 ot1 ot2 man ev1 ev2 ev3 ot1 ot2 para (2) In the parameter setting display mode, keep the [para] key pressed for 2 sec. or longer. >> The display is then changed to the setup setting display. pv sp mode rdy para (3) Press the [para] key several times. >> Display the setup setting [C14:Control action (Direct/Reverse)]. pv sp mode rdy para < < (4) Press the [<], [ ], or [ ] key to set the value you have selected from the following in [C14]. 0: Reverse action (Heat control) 1: Direct action (Cool control) >> When no keys are pressed for 2 sec. or longer, the flashing of the numeric value is stopped to set the currently displayed value. (5) Press the [mode] key. >> The display is returned to the operation display. Handling Precautions • When the setup setting [C26: Heat/cool control selection] is set at [1: Enabled], [C14] is not displayed. • The reverse action (heat control) means that the MV (manipulated variable) is decreased (or turned OFF) as the PV value increases. The direct action (cool control) means that the MV (manipulated variable) is increased (or turned ON) as the PV value increases. 5-8