Table 1: SIA requirements
Function
Default setting
Required setting
Entry delay
30 seconds
30 to 240 seconds
Exit delay
60 seconds
45 to 254 seconds
Dial delay
30 seconds
15 to 45 seconds
Auto-stay arm
On
On
Predial string
None
Set if reporting to central
station and customer has call
waiting service
Exit extension
On
On
Swinger shutdown
1 trip
1 to 2 trips
Smoke verify
Off
On
Duress code
Disabled
Disabled
Alarm verify/cross zoning
Disabled
Enabled for PIRs
Table 2 below describes nonprogrammable (hard coded) system operation
required to meet ANSI-SIA CP-01 and is provided only for reference.
Table 2: Nonprogrammable system operation
Function
Operation
Silent exit
All annunciators enabled
Remote arming exit time and
progress annunciation
All annunciators enabled
Abort annunciation
Enabled
Cancel report annunciation
Enabled
Recent closings
Enabled (two-minute window)
Exit error
Enabled
Central station reporting
The panel has been tested with the following central station receivers using SIA
and Contact ID reporting formats:
•
•
•
CS-5000 Central Station Receiver
Sur-Gard Central Station Receiver with models SG-DRL2A and SG-CPM2
Osborne-Hoffman OH 2000 Central Station Receiver
Allegro Control Panel Installation Manual