2.9 Feed Diagnostics
Select the link on the target chemical feed pump. The pump Diagnostic displays on the right.
The Time Modulate Special
Control is ON has 102
seconds ON time remaining
in its 120 second period.
The pump will be ON for a
maximum of 120 seconds
in every 120.
102 = 120 x (8-7.85)/(8-7)
The Inhibitor pump connected to
relay 1, last fed when the water
met
erc
onnect
edt
o‘
O’measur
ed
11400 Gallons.
Next feed occurs @ 11500
gallons.
Today, the pump has been ON
for 49.4 minutes
The bleed solenoid
connected to relay2,
prebleeds and then locks out
whenever the Biocide pump
connected to relay 3
pumps biocide
Sidebar:
AEGIS controllers are Diagnostic intensive.
Each sensor, water meter , contact set, relay-frequency output and the controller itself has a
Diagnostic display sequence.
Diagnostic tells you a lot about the operation of the treatment system and is invaluable if you
have a configuration problem or feed fault.
Even if you have Passwords turned ON, any user can still view the Diagnostics.
An uniformed user reading you the Diagnostic screen sequence may save you a site trip.
Browser access available locally or remotely via a VPN or modem connection displays all
controller Diagnostics.
Aegis _Browser 8/08